TradeCalculator.co.uk
Radiator Output Comparison — Type 11-22
Compare Type 11, Type 21 and Type 22 radiator BTU and watt outputs by size, with correction factors for heat pump flow temperatures.
Output Comparison (600mm High Radiators at ΔT50)
| Width | Type 11 (Watts) | Type 21 (Watts) | Type 22 (Watts) |
|---|---|---|---|
| 400mm | ~350W | ~510W | ~620W |
| 600mm | ~530W | ~760W | ~930W |
| 800mm | ~700W | ~1,020W | ~1,240W |
| 1000mm | ~880W | ~1,270W | ~1,550W |
| 1200mm | ~1,060W | ~1,520W | ~1,860W |
| 1400mm | ~1,230W | ~1,780W | ~2,170W |
| 1600mm | ~1,410W | ~2,030W | ~2,480W |
Correction Factors for Flow Temperature
| Flow/Return Temp | Delta T | Correction Factor | System |
|---|---|---|---|
| 75°C / 65°C | ΔT50 | 1.00 | Standard gas boiler |
| 65°C / 55°C | ΔT40 | 0.75 | Low-temp gas boiler |
| 55°C / 45°C | ΔT30 | 0.52 | High-temp heat pump |
| 50°C / 40°C | ΔT25 | 0.41 | Heat pump typical |
| 45°C / 40°C | ΔT22.5 | 0.36 | Efficient heat pump |
Physical Dimensions
- Type 11 — ~65mm deep, slimmest profile, suits tight spaces
- Type 21 — ~85mm deep, flat front panel, good balance of output and depth
- Type 22 — ~105mm deep, highest output, protrudes furthest from wall
Related Calculators
Use the Radiator Sizing Calculator for room heat loss, or the Radiator BTU Calculator for output requirements.
Next up: related pages
How We Calculate This
Frequently Asked Questions
The first digit is the number of panels, the second is the number of convector fins. Type 11 = 1 panel + 1 convector (slimmest, lowest output). Type 21 = 2 panels + 1 convector (good output, moderate depth). Type 22 = 2 panels + 2 convectors (highest output, deepest). A Type 21 produces roughly 40-50% more heat than a Type 11 of the same dimensions, and a Type 22 produces about 70-80% more than a Type 11.
Yes. UK radiator outputs are quoted at Delta T 50 (ΔT50) — meaning a mean water temperature 50°C above room temperature. This equates to flow 75°C, return 65°C, room 20°C. This is standard for gas boiler systems. Heat pump systems typically run at flow 45°C, return 40°C, giving ΔT22.5, at which radiators produce only about 35-40% of their rated output.
Use the EN 442 correction factor formula: actual output = rated output × (ΔT actual / ΔT 50)^1.3. For a heat pump at ΔT22.5: correction factor = (22.5/50)^1.3 = 0.36. So a radiator rated at 1,000W at ΔT50 would produce only 360W at ΔT22.5. This is why heat pump installations often need larger radiators — typically 2-3 times the rated size.
Type 22 radiators are generally best for heat pump systems because they provide the highest output per unit of wall space. Since heat pump flow temperatures are lower, you need maximum radiator surface area. Alternatively, consider oversized Type 21 radiators which are less bulky while still providing adequate output. Underfloor heating is the ideal emitter for heat pumps.
As a rough guide: 40-60 BTU per cubic foot of room volume, depending on insulation level and exposure. A typical 4m x 5m x 2.4m living room (48 m³ / ~1,700 ft³) needs approximately 4,500-6,000 BTU. Use a proper heat loss calculation for accuracy — this accounts for insulation, glazing, external walls and ventilation. A room heat loss calculator gives a much more accurate figure than rules of thumb.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.