Drainage Gradient Calculator — Fall, Invert Levels & Compliance

Check or calculate drainage gradients for foul and surface water pipes against Building Regulations Part H minimum and maximum falls.

Horizontal distance of pipe run

Invert level at start (upstream)

Invert level at end (downstream)

How We Calculate This

This calculator checks drainage gradients against Part H minimum requirements or calculates the required end invert level for a compliant gradient.

The formula

Gradient = (Start Invert - End Invert) / Pipe Length

Fall per metre (mm/m) = Gradient × 1000

AD H 2015 Table 6 minimum (flattest) foul gradients

  • 100mm foul: 1:80 (12.5mm/m) with ≥1 WC; 1:40 only if peak flow <1 l/s
  • 150mm foul: 1:150 (6.7mm/m) with ≥5 WCs
  • 100mm surface: 1:100 (10mm/m)
  • 150mm surface: 1:150 (6.7mm/m)