Septic Tank Sizing Calculator — What Size Septic Tank Do I Need?
Calculate the minimum septic tank capacity using the Approved Document H 2015 formula and drainage field area. Compliant with the General Binding Rules 2020.
Or use bedrooms + 1 as population equivalent
Enter a quoted price for reference
AD H 2015 §1.18 minimum for up to 4 users (default 2,700 litres)
Assumed daily wastewater per person (default 150 L/day)
Practical maximum trench length (BS 6297 allows up to 30m per leg; 15m used as a conservative default). AD H 2015 sets no trench-length limit.
Next up: related pages
How We Calculate This
This calculator uses the Approved Document H 2015 §1.18 formula to determine the minimum septic tank capacity and also calculates the required drainage field area based on the soil percolation rate.
Septic tank capacity formula (AD H 2015 §1.18)
C = 2,700 + 180 × (P − 4) litres, with a minimum of 2,700 litres (P = users)
Where P is the population equivalent (bedrooms + 1). A tank serving up to 4 users must be at least 2,700 litres; each user beyond 4 adds 180 litres. Desludging frequency does not reduce this minimum (the older BS 6297 "÷2 for biannual" rule is not in Approved Document H and would under-size the tank).
Drainage field sizing
Drainage field area = P × Vp × 0.25 m²
Where Vp is the percolation value (seconds per mm) determined by a percolation test — work yours out with our percolation test calculator, which also covers what a percolation test costs in the UK. The area is divided into trenches, 300–900mm wide at the base, with a minimum of 2 trenches (this tool uses ~15m per trench as a conservative default; BS 6297 permits up to 30m per leg, and AD H 2015 sets no trench-length limit). Per AD H 2015 §1.42, 2m of undisturbed ground must be maintained between parallel trenches; §1.40 limits the gradient to no steeper than 1:200.
Standards
Tank capacity and drainage-field area are set by Approved Document H 2015 (§1.18 capacity and §1.44 drainage-field floor area). Drainage-field design and installation should also follow BS 6297 (Code of Practice for the Design and Installation of Drainage Fields for Use in Wastewater Treatment). The installation must meet the General Binding Rules (England) 2020 for properties not connected to mains drainage, and the tank itself must comply with BS EN 12566-1.
Frequently Asked Questions
For a 3-bedroom house the population equivalent is 4 (bedrooms + 1). Per Approved Document H 2015 §1.18 a septic tank must be at least 2,700 litres for up to 4 users (C = 2700 + 180×(P−4)), so a 4-person tank = 2,700 litres. In practice you would install the nearest standard manufactured size (e.g. 2,800 or 3,000 litres). Desludging frequency does not reduce the AD H minimum capacity.
Approved Document H 2015 §1.18: a septic tank should have a capacity below the inlet of at least 2,700 litres for up to 4 users, increased by 180 litres for each additional user — i.e. C = 2700 + 180×(P−4), with a 2,700 L floor. (This is the current statutory rule and supersedes the older 'C = 2000 + 180P' form sometimes attributed to BS 6297; desludging frequency does not reduce the required capacity.)
No. Since 1 January 2020 under the General Binding Rules (England), septic tanks can no longer discharge directly to a watercourse (stream, river, ditch). The effluent must be treated through a drainage field (soakaway) or you must upgrade to a sewage treatment plant. Existing septic tanks that discharge to a watercourse must be replaced or upgraded when the property is sold. See our Sewage Treatment Plant Calculator if you need to upgrade.
Septic tanks should be desludged at least once per year. Note the Approved Document H minimum capacity (2,700 L for up to 4 users, +180 L per extra user) is not reduced by more frequent desludging — under-sizing for a desludging schedule is the unsafe direction. Regular desludging prevents overflow that can block the drainage field and cause expensive repairs. A tanker visit typically costs £150-£300.
A drainage field (also called a soakaway system) is a network of perforated pipes buried in gravel-filled trenches that allows septic tank effluent to percolate into the surrounding soil for final treatment. The size depends on the number of residents and the soil percolation rate (Vp value). The formula is: Area = P × Vp × 0.25 m². A percolation test must be carried out to determine the Vp value before designing the drainage field.
Related Calculators
Was this calculator helpful?
Last updated: February 2026