Prospective Fault Current Calculator — BS 7671
Calculate prospective short circuit current (PSCC) and prospective earth fault current (PEFC) from loop impedance values per BS 7671:2018+A4:2026 (18th Edition) Regulation 434.5.1.
Measured at origin of installation
One-way cable run length
Resistance per metre of line conductor
Resistance per metre of neutral conductor
Resistance per metre of circuit protective conductor
Nominal supply voltage
Breaking capacity of protective device
Safety notice
Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.
Next up: related pages
How We Calculate This
This calculator determines the maximum prospective fault current at the origin and at any point in a circuit using Ohm's law applied to the fault loop impedance, with the voltage factor Cmax = 1.10 applied per BS 7671:2018+A4:2026 Appendix 3 / IEC 60909.
Prospective fault current formula
At the origin: PSCC = Cmax × Uo / Ze, where Uo is the nominal line-to-neutral voltage (230V single phase), Cmax = 1.10 (so 230V × 1.10 = 253V) and Ze is the external earth fault loop impedance.
At any point: PEFC = Cmax × Uo / Zs, where Zs = Ze + R1 + R2 (the total line-earth loop impedance including circuit conductor resistances).
The Cmax = 1.10 factor is a conservative design upper bound: ESQCR permits the 230V supply to sit up to +10% high (253V), so the calculated fault current is the worst case. It reads roughly 10% higher than a hand-held PFC tester, which measures at the actual supply voltage with no voltage factor applied.
Breaking capacity
BS 7671:2018+A4:2026 Regulation 434.5.1 requires the rated breaking capacity of each protective device to be not less than the prospective fault current at its point of installation. A device with a lower breaking capacity is still permitted where adequate upstream (back-up) protection limits the let-through energy, or where the assembly carries a conditional short-circuit rating. The calculator compares the unconditional PSCC at the origin against the device breaking capacity.
- MCBs to BS EN 60898: commonly 6kA, sometimes 10kA (suitable for most domestic supplies)
- BS 88-3 HRC fuses: up to 80kA breaking capacity
- BS 1361 Type I consumer-unit cartridge fuse: 16.5kA at 240V
- BS 1361 / BS 88-3 Type II house-service cut-out: 33kA at 415V (ASTA-enhanced to 80kA)
- Domestic consumer unit (BS EN 61439-3): commonly 16kA conditional rating behind a 100A BS 88-3 service cut-out
Frequently Asked Questions
Prospective fault current is the maximum current that would flow during a short circuit or earth fault. BS 7671:2018+A4:2026 (18th Edition) Regulation 434.5.1 requires that the prospective fault current be determined at every point of the installation. Each protective device should have a breaking capacity at least equal to the prospective fault current at its point of installation. A device with a lower breaking capacity may still comply where an upstream device limits the let-through energy (back-up protection) or where the assembly carries a conditional short-circuit rating — but otherwise it may fail to safely interrupt the fault and could cause fire or damage.
PSCC (Prospective Short Circuit Current) is the fault current that flows in a line-to-neutral short circuit. PEFC (Prospective Earth Fault Current) is the fault current that flows in a line-to-earth fault via the circuit protective conductor. PSCC is typically higher because the neutral conductor usually has lower impedance than the CPC. Both must be checked against the protective device's breaking capacity.
Maximum prospective fault current is calculated using Ohm's law with the voltage factor Cmax: Ipf = Cmax × Uo / Zs, where Uo is the nominal line-to-neutral voltage (230V single phase), Cmax = 1.10 and Zs is the loop impedance. The 1.10 factor accounts for the supply being permitted to sit up to +10% high (230V × 1.10 = 253V), so at the origin PSCC = 253 / Ze. At any point in the circuit, the conductor resistances (R1, Rn or R2) are added to Ze. Because Cmax assumes the worst-case high voltage, this calculator reads roughly 10% higher than a hand-held PFC tester, which measures at the actual supply voltage.
Standard domestic MCBs typically have a 6kA breaking capacity, which is adequate for most domestic installations where PSCC is usually below 6kA. For installations close to substations or with very low Ze values, the PSCC may exceed 6kA and MCBs with higher breaking capacity (10kA or 16kA) or HRC fuses (BS 88 with 80kA) may be required. Use our Circuit Breaker Sizing Calculator to select the right MCB rating.
TN-C-S (PME) systems typically have Ze values between 0.2 and 0.35 ohms. TN-S (lead sheath) systems typically range from 0.35 to 0.8 ohms. TT systems can have much higher values. The DNO (Distribution Network Operator) can provide the maximum expected Ze for your supply. Lower Ze means higher prospective fault current at the origin.