TradeCalculator.co.uk
Voltage Drop Calculator — UK Wiring Regulations
Check your cable voltage drop complies with BS 7671 18th Edition limits. UK supply is 230V with 3% limit for lighting and 5% for other circuits.
Design current or MCB rating
Distance from consumer unit to furthest point
UK nominal supply (default 230V)
Max voltage drop for lighting (default 3%)
Max voltage drop for other circuits (default 5%)
Safety notice
Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.
Next up: related pages
How We Calculate This
This calculator uses voltage drop data from BS 7671 18th Edition tables to determine whether your cable run complies with UK wiring regulations. Voltage drop occurs because all conductors have resistance, and the longer the cable run, the more voltage is lost.
The formula
Voltage Drop (V) = (mV/A/m × Current × Length) ÷ 1000
For example, a 2.5mm² twin and earth cable has a voltage drop rate of 18 mV/A/m. If you draw 20A over a 15m run: (18 × 20 × 15) ÷ 1000 = 5.4V drop, which is 2.3% of 230V — well within the 5% limit for power circuits.
UK limits per BS 7671
- Lighting circuits: Maximum 3% voltage drop (6.9V on 230V supply)
- Other circuits: Maximum 5% voltage drop (11.5V on 230V supply)
Three-phase circuits
The tabulated mV/A/m figure is the single-phase (two-conductor) drop. On a balanced three-phase circuit the line-to-line drop is √3÷2 (about 0.866) of that value, and the result is checked against the 400V line-to-line supply rather than 230V. This calculator applies the 0.866 factor automatically when you select three-phase.
These limits apply from the origin of the installation to the furthest point of the circuit. If the voltage drop exceeds these limits, you need to increase the cable size or reduce the circuit length. The mV/A/m values used are from BS 7671 Table 4D5 for flat twin and earth (6242Y, tabulated up to 16mm²) and Table 4D4B for multicore steel wire armoured (SWA) cables.
Working figures for this are collected in our Voltage Drop Coefficients reference table.
Frequently Asked Questions
BS 7671 18th Edition limits voltage drop to 3% for lighting circuits (6.9V on a 230V supply) and 5% for all other circuits (11.5V on a 230V supply). These limits apply from the origin of the installation (typically the meter) to the furthest point of the circuit.
There are two main ways: increase the cable size (a larger cross-sectional area has lower resistance) or reduce the cable length. For very long runs, such as to an outbuilding, you may need to go up one or two cable sizes beyond what the current capacity requires. SWA cable may also help as it can handle longer runs. Use our Cable Sizing Calculator to find the right cable for your current and installation method.
For typical domestic cable runs under 10-15 metres, voltage drop is rarely an issue. It becomes critical for longer runs such as garden buildings, EV chargers at the end of a long drive, or commercial installations. Always check both current capacity and voltage drop. Use our Cable Length Calculator to determine the actual cable run distance, then confirm the cable's current-carrying capacity holds up in its installed conditions with our Cable Derating Calculator (temperature, grouping and thermal-insulation factors).
mV/A/m stands for millivolts per amp per metre. It is the voltage drop rate for a given cable size listed in the BS 7671 appendix 4 tables — Table 4D5 for flat twin and earth (6242Y) and Table 4D4B for multicore steel wire armoured (SWA). The single-phase formula is: Voltage drop (V) = (mV/A/m x current x length) / 1000. For a balanced three-phase circuit the line-to-line drop is 0.866 (the square root of 3, divided by 2) times that single-phase value.
The UK nominal supply voltage is 230V +10% / -6% as harmonised with European standards. In practice, most UK supplies still deliver around 240V at the meter. BS 7671 calculations use 230V as the reference. A measured supply of 240V gives slightly more headroom on voltage drop limits.
Related Guides & Answers
Related Calculators
Was this calculator helpful?
Last updated: February 2026
Verified against UK standards · estimates only, confirm with your supplier.