Calculate the type, quantity and placement of portable fire extinguishers per BS 5306-8:2023 — Class A provision sized per storey at 0.065 × floor area (26A minimum), plus CO2 for electrical and wet chemical for kitchens.

Usable floor area of one storey (sizing is per storey)

Total above-ground storeys

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator determines the type and quantity of portable fire extinguishers from floor area and the identified fire hazards, following BS 5306-8:2023.

How it works

  • Required rating per storey: Aggregate Class A rating = 0.065 × floor area of the storey (m²), rounded up, with a minimum of 26A. A 400 m² storey needs 26A.
  • Minimum count: At least two extinguishers per storey over 50 m²; one high-rated unit is allowed on a storey of 50 m² or less (BS 5306-8:2023).
  • Unit coverage: A 13A extinguisher covers about 200 m² (13 ÷ 0.065), 21A about 323 m², 34A about 523 m². Enough units are provided for their combined rating to meet the per-storey requirement, then multiplied across all storeys.
  • Primary provision: Water or foam extinguishers for general Class A risk (dry powder is not generally recommended indoors).
  • Supplementary: CO2 within 10 m of electrical risks; wet chemical within 2 m of kitchen cooking appliances.
  • Travel distance: Maximum 30 m to a Class A extinguisher; 10 m for electrical and Class B (special) risks.