Background Ventilation Calculator — Part F Trickle Vents

Calculate minimum whole dwelling ventilation rate, trickle ventilator equivalent areas per room, and purge ventilation openings per Approved Document F 2021 Tables 1.3, 1.7 and 1.4.

8000 mm² EA each

8000 mm² EA each

4000 mm² EA each (wet room)

4000 mm² EA each

4000 mm² EA each

How We Calculate This

This calculator determines background ventilation requirements per Approved Document F (2021) System 1 (background ventilators with intermittent extract).

ADF 2021 Table 1.3 — whole dwelling rates

  • 1 bedroom: 19 L/s
  • 2 bedrooms: 25 L/s
  • 3 bedrooms: 31 L/s
  • 4 bedrooms: 37 L/s
  • 5 bedrooms: 43 L/s (add 6 L/s per extra bedroom)
  • Or 0.3 L/s per m² internal floor area (whichever is greater)

ADF 2021 Table 1.7 — trickle vent EA

  • Habitable rooms & kitchen: 8000 mm² EA each (10,000 in single-storey dwellings)
  • Bathroom: 4000 mm² EA; utility room & WC: no minimum