Flue Liner Calculator — What Size Flue Liner Do I Need?
Calculate the correct flue liner diameter, length, and insulation for wood burners, multi-fuel stoves and gas fires per UK Building Regs Approved Document J.
From stove connection to chimney top
Nominal heat output — check stove spec sheet
Flue can never be smaller than the outlet (AD J 2.5)
Internal width of chimney void. Standard: 225mm
Bends in Flue Route
Each adds ~0.5m to liner length
Each adds ~1.0m to liner length. Avoid if possible.
If exempt and ≤20kW, AD J Table 2 allows a 125mm (5in) flue. Check the manual.
Recommended — improves draught and reduces condensation
Enter price per metre for a liner cost estimate
Extra liner length per 45° bend (default 0.5m)
Extra liner length per 90° bend (default 1.0m)
Minimum total flue height for adequate draught (default 4.5m)
Next up: related pages
How We Calculate This
This calculator determines the correct flue liner diameter based on your stove output and fuel type, then calculates the total liner length needed (including allowance for bends), and estimates vermiculite insulation bags.
Flue liner sizing (Approved Document J, Table 2)
- Closed appliance up to 30kW, any fuel: minimum 150mm (6") diameter
- Closed appliance above 30kW and up to 50kW, any fuel: minimum 175mm (7") diameter
- Above 50kW: not tabulated in AD J — size by design to BS EN 13384-1
- Clean Air Act / DEFRA-exempt appliance up to 20kW (smokeless/low-volatiles): minimum 125mm (5") diameter
- Gas fire/stove (AD J Table 5): minimum 125mm (5") diameter
The flue must never be smaller than the appliance outlet collar (AD J paras 2.4–2.5), and the appliance manufacturer's installation manual always takes priority.
Liner length calculation
Total liner length = Chimney height + Bend allowances
- Each 45-degree bend adds approximately 0.5m
- Each 90-degree bend adds approximately 1.0m
- Approved Document J: flues should be as straight and vertical as possible, with any bends angled no more than 45° to the vertical
- No more than four changes of direction in total (each up to 45°) — a 90° factory-made bend, elbow or tee counts as two 45° bends (AD J, Bends in flues / Diagram 15)
Vermiculite insulation
Vermiculite is poured into the void between the flue liner and the chimney wall. The volume needed is the annular cross-section (chimney void area minus the round liner area) multiplied by the chimney height, with a small allowance for settling and taper. There is no single "metres per bag" figure — it depends on the void size and liner diameter — so the calculator derives the bag count from this geometry. Tell it whether the void is round (clay-lined) or square/rectangular (brick), because a square flue holds about 27% more vermiculite than a round one of the same width.
Chimney height requirements
A minimum total flue height of about 4.5m can give adequate draught (AD J para 2.8). The flue must terminate at least 600mm above the ridge if it passes through the roof at or within 600mm of the ridge; elsewhere it must be at least 2.3m horizontally from the roof and either 1m above where the chimney meets the roof or as high as the ridge (Approved Document J, Diagram 17).
Standards
UK Building Regulations Approved Document J (Combustion appliances and fuel storage systems). Flue liners per BS EN 1856-2 (metal liners). Flue system design per BS EN 15287.
Frequently Asked Questions
Per Approved Document J Table 2: a closed appliance (stove) burning any fuel up to 30 kW requires a minimum 150 mm (6") diameter flue, above 30 kW and up to 50 kW requires 175 mm (7"), and appliances above 50 kW must be sized by design to BS EN 13384-1 (AD J does not tabulate them). Gas fires/stoves need 125 mm (5"). A 125 mm (5") flue is allowed only for a Clean Air Act / DEFRA-exempt appliance up to 20 kW burning smokeless or low-volatiles fuel. In every case the flue must never be smaller than the appliance outlet collar, and the manufacturer's installation manual takes priority. Use our Stove Flue Calculator for complete flue system sizing.
Your flue liner needs to run from the stove connection at the base of the chimney to the top of the chimney pot, plus extra length for any bends. Add approximately 0.5m for each 45-degree bend and 1.0m for each 90-degree bend. The total flue height from stove to terminal should be at least 4.5m for adequate draught. Buy liner in one continuous length where possible.
Yes, insulating a flue liner is strongly recommended and often required by Building Control. Insulation (usually vermiculite granules poured around the liner in the chimney void) keeps flue gases hot, improving draught and reducing condensation and tar build-up. There is no fixed coverage figure — the number of bags depends on the chimney cross-section, its shape, and the liner size, so always work it out from the geometry rather than a flat rule of thumb. This calculator does that from the annular volume (chimney void area minus liner area, times height, plus a settling allowance). For a 150mm liner the coverage of a 100-litre bag ranges from roughly 4m per bag in a narrow 225mm round clay-lined flue down to only about 2m per bag in a wider 250mm square brick flue — square brick flues hold noticeably more vermiculite than round ones of the same width, so they need more bags per metre.
A register plate is a metal plate that seals across the fireplace opening just above the stove, through which the flue liner passes. It is essential for all stove installations — it prevents soot, debris and cold air from falling into the room, and ensures all combustion gases go up through the liner. Approved Document J does not specify a plate thickness; as a practical rule it is made from galvanised or stainless steel, typically 1–2mm thick, and must be robust enough to support the weight of any vermiculite poured above it.
Per Approved Document J (Diagram 17, solid-fuel appliances), a flue must terminate at least 600mm above the ridge if it passes through the roof at or within 600mm of the ridge. Elsewhere on the roof it must be at least 2,300mm (2.3m) horizontally from the nearest point on the roof, and either at least 1,000mm above the highest point where the chimney meets the roof or at least as high as the ridge. The outlet must also be at least 1,000mm above the top of any openable rooflight, dormer window or other opening within 2.3m, and at least 600mm above any adjacent building within 2.3m.