TradeCalculator.co.uk
Earth Electrode Resistance — TT System Reference
Target earth electrode resistance values for TT earthing systems, soil resistivity by type, testing methods and seasonal variation guidance per BS 7671.
Target Earth Electrode Resistance Values
| RCD Rating (mA) | Max Ra for 50V (ohms) | Recommended Max (ohms) |
|---|---|---|
| 30 | 1667 | 200 |
| 100 | 500 | 200 |
| 300 | 167 | 100 |
| 500 | 100 | 50 |
Ra × Ia must not exceed 50V per BS 7671 Regulation 411.5.3 (TT systems).
Soil Resistivity by Type
Soil resistivity directly affects earth electrode resistance. Lower resistivity soils give lower electrode resistance.
| Soil Type | Resistivity (ohm-metres) | Typical Electrode Ra* |
|---|---|---|
| Marshy ground, peat | 5 – 40 | 2 – 15 |
| Clay (wet) | 8 – 50 | 3 – 20 |
| Clay (dry) | 50 – 150 | 20 – 60 |
| Loam, garden soil | 50 – 200 | 20 – 80 |
| Sand (wet) | 100 – 300 | 40 – 120 |
| Sand (dry) | 1000 – 3000 | 400 – 1200 |
| Gravel | 300 – 1000 | 120 – 400 |
| Chalk | 100 – 500 | 40 – 200 |
| Limestone | 500 – 10,000 | 200 – 4000 |
| Rock (granite, slate) | 1000 – 100,000 | 400+ |
* Typical Ra for a single 2.4m driven rod. Multiple rods or longer rods will reduce resistance.
Methods to Reduce Earth Resistance
- Drive rods deeper — doubling length reduces resistance by approximately 40%
- Use multiple rods in parallel — spaced at least their depth apart (e.g., 2.4m rods at 2.4m spacing)
- Use earth enhancement compounds (e.g., bentonite, Marconite) around the electrode
- Install earth plates or earth mats for very high resistivity soils
- Locate electrodes in the wettest available ground
Seasonal Correction Factors (UK)
| Season Tested | Correction Factor |
|---|---|
| Winter (wet) | 1.5 – 2.0 |
| Spring/Autumn | 1.0 – 1.3 |
| Summer (dry) | 1.0 (worst case) |
Apply the factor to a winter reading to estimate summer worst-case values.
Related Pages
See the BS 7671 Domestic Circuit Guide and the BS 7671 18th Edition Changes for RCD requirements in TT systems. Use the Earthing System Calculator to work out electrode resistance from the BS 7430 rod formula.
Next up: related pages
Frequently Asked Questions
For a TT system protected by a 30mA RCD (the most common arrangement in the UK), the earth electrode resistance must not exceed 1667 ohms (calculated as 50V ÷ 0.03A). However, a maximum of 200 ohms is widely recommended as good practice to ensure reliable RCD operation and provide adequate fault current. BS 7671 Regulation 411.5.3 requires that Ra × Ia ≤ 50V, where Ra is the total earth fault loop impedance and Ia is the RCD operating current.
Earth electrode resistance is tested using a dedicated earth electrode tester (e.g., Megger DET4) with the fall-of-potential method. Two temporary test spikes are driven into the ground in a straight line from the electrode under test. The potential spike is placed at 61.8% of the distance to the current spike (the 61.8% rule). At least three readings should be taken at different spike positions to verify consistency. Testing should be done in dry conditions for worst-case results.
Yes, earth electrode resistance varies seasonally. It is lowest in winter when the ground is wet and highest in late summer when the soil is driest. Resistance can vary by a factor of 2-3 between wet and dry seasons. For this reason, testing in dry conditions gives the most conservative (worst-case) result. If tested in winter, apply a seasonal correction factor — typically 1.5 to 2.0 for UK conditions.
The most common earth electrode in the UK is a driven copper-clad steel rod, typically 1.2m sections that can be coupled together and driven to 2.4m or deeper. Earth rods should be at least 16mm diameter for copper-clad steel. Alternatives include earth plates (minimum 0.5m², 2mm thick copper), earth tapes (minimum 25mm × 2mm copper strip), and foundation earth electrodes. The choice depends on soil conditions and the target resistance.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.