Conduit & Trunking Fill Calculator — BS 7671
Calculate cable fill for conduit and trunking installations. Check space-factor compliance using the IET On-Site Guide Appendix E (cable, conduit and trunking factors) — the guidance referenced by BS 7671.
Total number of this cable type
IET space-factor cap: 35% conduit, 45% trunking
Reduces allowable fill (rule of thumb, not an IET figure). Max 2 bends recommended between draw points; size from Appendix E factor tables for bent runs
Safety notice
Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.
Next up: related pages
How We Calculate This
This calculator checks whether the cables you want to install will fit within the chosen conduit or trunking size without exceeding the recommended space factor limit.
Space factor calculation
Space factor = (Total cable CSA / Enclosure internal CSA) × 100%. The recommended maximum space factor is 35% for conduit and 45% for trunking (IET On-Site Guide / Guidance Note 1, Appendix E). The old 40% conduit figure was superseded as arbitrary.
Step 1:Determine the internal cross-sectional area of the conduit or trunking from the manufacturer's data or standard sizes.
Step 2: Calculate the total cross-sectional area of all cables to be installed (including insulation and sheath).
Step 3: Compare the space factor against the limit for the enclosure (35% conduit, 45% trunking). If exceeded, upsize the conduit/trunking or split the cables across multiple runs. For conduit runs with bends, the IET On-Site Guide Appendix E unit cable-factor and conduit-factor tables are the definitive method.
Common conduit sizes
- 20mm: Most common for domestic circuits, 2-3 cables typically
- 25mm: Used for larger cable groups or longer runs
- 32mm: Commercial installations with multiple circuits
Working figures for this are collected in our UK Conduit Sizes & Cable Fill reference table.
Frequently Asked Questions
The IET On-Site Guide and Guidance Note 1 (Appendix E) set a maximum space factor of 35% for conduit where the cable is not covered by the unit factor tables. This means the total cross-sectional area of all cables inside the conduit should not exceed 35% of the internal cross-sectional area of the conduit. The older 40% conduit figure was an arbitrary value later shown to be inappropriate (IET, Wiring Matters, November 2021). The 35% headroom allows for cable pulling, heat dissipation and future additions. Capacities of conduit and trunking have not been in BS 7671 itself since 1991 — the committee treats them as guidance, published in the IET On-Site Guide / Guidance Note 1.
Trunking has a higher recommended maximum space factor of 45% (IET On-Site Guide / Guidance Note 1, Appendix E). Because trunking is rectangular and cables can be laid flat, the arrangement can be more efficient than round conduit, so a 45% fill is permitted versus 35% for conduit. The 45% rule still ensures cables are not packed too tightly and can dissipate heat properly.
Each bend in a conduit run makes it harder to pull cables through, so the practical allowable fill is lower than for a straight run. It is recommended to have no more than two 90-degree bends between draw points; if more are needed, install additional draw-in boxes. The bend reduction used by this calculator is a simplified rule of thumb, not an IET figure — for runs with bends the definitive method is the IET On-Site Guide Appendix E reduced cable-factor and conduit-factor tables, which switch to a different factor set keyed on run length and number of bends.
Yes, you can mix different cable sizes, but you need to add up the cross-sectional areas of all cables and ensure the total does not exceed the space-factor limit for the enclosure — 35% for conduit, 45% for trunking. This calculator works with one cable type at a time, so add the CSA values for each cable type together manually if mixing sizes. For conduit runs with bends, the IET On-Site Guide Appendix E unit cable-factor and conduit-factor tables are the definitive sizing method.
Conduit is typically used for individual circuit runs and where mechanical protection is needed in walls, floors and ceilings. Trunking is used where multiple circuits run along the same route, such as along walls in commercial premises. Trunking is easier to add cables to later and provides better separation between circuits when using compartmented trunking. See our dedicated Conduit Fill Calculator and Trunking Fill Calculator for detailed sizing, or check standard UK cable trunking sizes before choosing a run.