Skip to content

UK Cable Trunking Sizes & Capacity

Mini trunking and maxi trunking sizes with cable capacities, compartment options and installation guidance.

Mini Trunking Sizes

Mini Trunking Sizes
Size W x D (mm)Internal Area (mm²)45% Fill (mm²)Max. Cables (1.5 mm² T&E)
16 x 16~200~901
25 x 16~340~1532
38 x 16~530~2384
38 x 25~830~3737
40 x 25~870~3927

Maxi Trunking Sizes

Maxi Trunking Sizes
Size W x D (mm)Internal Area (mm²)45% Fill (mm²)Typical Use
50 x 50~2,100~945Small distribution runs
75 x 50~3,200~1,440Medium distribution
100 x 50~4,400~1,980Main distribution runs
100 x 75~6,700~3,015Heavy distribution
150 x 50~6,600~2,970Wide runs, compartmentalised
150 x 75~10,100~4,545Large installations

Cable Cross-Sectional Areas (for Fill Calculations)

Cable Cross-Sectional Areas (for Fill Calculations)
CableOverall Area (mm²)
1.0 mm² T&E (2 core + earth)~40
1.5 mm² T&E (2 core + earth)~52
2.5 mm² T&E (2 core + earth)~71
4.0 mm² T&E (2 core + earth)~94
6.0 mm² T&E (2 core + earth)~120
Cat 6 data cable~28

Worked Example: Checking Trunking Cable Fill

Trunking fill is checked by adding up the cross-sectional area of every cable, then comparing the total against 45% of the trunking internal area (see the tables above).

Example 1, mini trunking:three 2.5 mm² T&E cables in 25 x 16 mm mini trunking. Each cable is about 71 mm² (from the table above), so three cables total about 213 mm². The 45% usable area of 25 x 16 mm trunking is about 153 mm², so three cables do not fit within the limit; two cables (about 142 mm²) do fit. Step up to 38 x 16 mm, whose 45% usable area of about 238 mm² takes all three.

Example 2, maxi trunking:a run of twelve 2.5 mm² T&E cables in 100 x 50 mm maxi trunking. Total cable area is about 12 x 71 = 852 mm², against a 45% usable area of about 1,980 mm² for that size, well within the limit. In practice, physical fill is rarely the limiting factor once trunking reaches maxi sizes: current-carrying capacity and the BS 7671 Table 4C1 grouping factor for multiple circuits usually govern the design first.

These examples use the T&E overall areas shown in the table above, and internal areas reduced for wall thickness. The Trunking Fill Calculator works from nominal internal areas (25 x 16 mm as 400 mm² rather than 340 mm²) and covers 25 x 16, 40 x 16 and 40 x 25 in the mini range, so it will report a slightly different fill percentage for the same cables. Use it for an exact check against your own cable mix, and treat the lower internal areas here as the more conservative figure.

Related Calculators

See the Conduit Sizes for conduit cable fill, or the UK Cable Sizes for cable current ratings.

To check the fill percentage for your own cable list rather than the table figures above, use the Trunking Fill Calculator or the Conduit and Trunking Fill Calculator.

Frequently Asked Questions

Was this calculator helpful?

Last updated: April 2026

Verified against UK standards · estimates only, confirm with your supplier.