Fire Door Specification Calculator — FD30/FD60 Rating per Part B

Determine fire door ratings, ironmongery and intumescent requirements based on UK Building Regulations Approved Document B.

Total storeys including basements

Total fire doors to specify

Door is on an escape route

Escape route doors need additional signage

Door includes glazed panel

Fire-rated glazing will be specified if enabled

Safety notice

Fire safety measures must satisfy Approved Document B and often need building control approval. Confirm the final specification with building control or a fire engineer before relying on it.

How We Calculate This

This calculator determines the correct fire door specification based on Approved Document B of the UK Building Regulations, BS 476-22, and BS EN 1634-1. It considers the building type, number of storeys, door location and intended use to recommend the appropriate fire rating, ironmongery and sealing requirements.

How it works

  • Building type: Dwellings, flats, HMOs, commercial and care homes each have different fire door requirements under AD B.
  • Door location: The position of the door within the building determines the required fire rating. Flat entrance doors, compartment walls and stairway enclosures outside single family houses have the highest requirements. A protected stairway inside a single family dwellinghouse is the exception: Table C1 item 11(b) sets it at minimum E 20 (FD20) with no smoke seal, and item 4a excepts it from the E 30 Sa entry.
  • Building height: No row of Table C1 changes with building height. The one height rule in AD B is the firefighting shaft: where a building has a storey more than 18m above fire and rescue service vehicle access level, para 15.2 requires one or more firefighting shafts, and Diagram 15.1 gives that shaft enclosure E 60 Sa (FD 60 S) doorsets. That is the shaft door only. Other protected stairways in the same building stay at E 30 Sa (FD 30 S) under Table C1 item 4a. A typical 4-5 storey block (~12-15m) usually stays at FD30S. Longer periods otherwise reach a door only by inheritance, where a doorset in a compartment wall or floor takes the period of the element it sits in (Table C1 items 1, 2e and 3, via para C13 and Tables B1/B2). Always confirm with building control and the fire strategy.
  • Ironmongery: All components must be CE-marked and tested as part of the fire door assembly to BS EN 1634-1.

Key standards

  • Approved Document B: Fire safety requirements for buildings in England
  • BS 476-22: Fire resistance test for non-loadbearing elements
  • BS EN 1634-1: Fire resistance and smoke control tests for doors
  • BS EN 1154: Door closing devices specification