TradeCalculator.co.uk
Floor Insulation Calculator — Thickness & Quantities
Calculate floor insulation thickness to meet UK Building Regulations Part L. Mineral wool, PIR board and EPS quantities.
Longest dimension of the area
Shortest dimension of the area
Floor not a simple rectangle? An L-shaped floor is just two rectangles: measure each one wall to wall and add it as a section. Use three sections for a T or U shape. The calculator adds every section together.
Adds 10% for cutting and fitting around obstacles
10% standard, 15% if many pipes/obstacles
Polythene membrane for warm side of insulation
Enter your supplier price for a cost estimate
Internal surface resistance (default 0.17)
External air surface resistance, BS EN ISO 6946 (default 0.04). Applied to suspended floors only — ground-bearing floors have no external air surface
Area per rigid board (2400 × 1200mm = 2.88 m², default)
m² per pack of your slab. Leave blank to use Rockwool Flexi (1200 × 600mm) datasheet figures for the recommended thickness
Multiplier for VCL overlap allowance (default 1.15)
Next up: related pages
How We Calculate This
This calculator determines the insulation thickness needed to achieve your target U-value, then calculates the quantity of insulation material required including a wastage allowance.
For an L-shaped floor, press Add section and enter each rectangle as its own section. Boards and mineral-wool packs are rounded up per section and then added together, so the estimate covers the extra cuts where the sections meet and never under-orders, while the VCL membrane is worked out from the combined area. Use three sections for a T or U shape.
The formula (suspended floors)
For a suspended timber floor the U-value is a simple sum of layer resistances (BS EN ISO 6946):
R_insulation = (1 / U_target) − R_floor − R_si − R_se
Thickness = R_insulation × λ × 1000 (in mm)
Where:
- R_si = 0.17 m²K/W (internal surface resistance, downward heat flow — BS EN ISO 6946 surface-resistance design values, also reproduced in BRE BR 443)
- R_se = 0.04 m²K/W (external air surface resistance, suspended floors only)
- R_floor = typical/indicative element resistance, varies by construction type
Ground-bearing floors
Solid concrete and beam-and-block floors are not sized this way. Their heat loss depends on the perimeter-to-area ratio and the resistance of the ground, so the U-value must be found with the BS EN ISO 13370 method (BRE BR 443). The thickness shown here for those floor types uses the simpler layer sum and is conservative (over-stated) — confirm it with a full ISO 13370 calculation.
Insulation lambda (λ) values
- Mineral-wool slab (Rockwool Flexi): 0.038 W/mK at 50-120mm, 0.035 W/mK at ≥140mm (BS EN 13162). Sold as a single slab up to 180mm — thicker build-ups use two layers
- PIR Board (Celotex GA4000-grade): 0.022 W/mK
- Phenolic Board (Kingspan Kooltherm K103): 0.019 W/mK
- EPS 70: 0.038 W/mK
- Spray Foam (closed-cell PU): 0.025 W/mK
λ values are declared figures from current manufacturer datasheets; always confirm against the specific product and BBA certificate you are buying.
Frequently Asked Questions
UK Building Regulations Part L 2021 requires a U-value of 0.18 W/m²K or better for new-build ground floors. For renovation of existing ground floors (threshold trigger 0.70 W/m²K), the improved target is 0.25 W/m²K. Some energy schemes like Passivhaus target 0.15 W/m²K or better.
The most common method is to fit mineral wool batts or rigid PIR boards between the joists from below (if accessible via a cellar or crawl space) or from above after lifting floorboards. Support the insulation with netting stapled to the joists. A vapour control layer should be fitted on the warm (room) side.
To achieve the Part L 2021 new-build target of 0.18 W/m²K on a suspended timber floor: PIR board (Celotex GA4000-grade, λ 0.022) needs about 110mm (a 120mm board), phenolic board (Kingspan Kooltherm K103, λ 0.019) about 95mm (a 100mm board), mineral-wool slab (Rockwool Flexi, λ 0.035 at ≥140mm) about 175-180mm (a 180mm slab, the thickest single Flexi slab), and EPS 70 (λ 0.038) about 190mm (a 200mm board). For the renovation target of 0.25 W/m²K, PIR needs about 75-80mm. These figures use the simple layer-sum method, which is correct for suspended floors; solid concrete and beam-and-block floors must be sized with the BS EN ISO 13370 ground-floor method instead.
For suspended timber floors, yes — a VCL (polythene membrane) should be installed on the warm side of the insulation to prevent moisture from the room condensing within the insulation. For solid concrete floors, the DPM (damp proof membrane) serves this function. Overlap all VCL joints by 150mm and tape all seams.
Split the floor into rectangles and enter each one as its own section using the Add section button; the calculator adds the areas together for you. Rigid boards and mineral-wool packs are worked out per section and rounded up before being added, which covers the extra cutting where the sections meet and never under-orders. The VCL membrane is priced on the combined floor area, while the VCL tape estimate uses each section's full perimeter, which slightly over-counts at the join, so treat it as a safe upper figure. The insulation thickness itself does not change with room shape. Use three sections for a T or U shaped floor.
Rigid PIR boards (Celotex GA4000-grade, λ 0.022 W/mK) and phenolic boards (Kingspan Kooltherm K103, λ 0.019 W/mK) achieve the required U-value with much less thickness than mineral-wool slab (Rockwool Flexi, λ 0.038 W/mK at 50-120mm, improving to 0.035 W/mK at 140mm and above). However, mineral wool is cheaper, easier to cut around pipes and services, and provides better acoustic insulation. Where depth between joists is limited, a rigid board is often the better choice.
Unlike a suspended floor, a ground-bearing floor cannot be sized by simply adding up the resistances of its layers. Heat is lost to the ground at the edges, so the U-value depends on the floor's perimeter-to-area ratio as well as its construction. The governing standard is BS EN ISO 13370 (with the conventions in BRE BR 443), which is referenced by Approved Document L. The same insulation thickness gives a different U-value for a small floor than for a large one. The thickness this calculator shows for solid concrete or beam-and-block floors uses the simpler layer-sum method, which ignores the ground's resistance and therefore over-states the insulation needed — treat it as a conservative starting point and confirm the final specification with a full ISO 13370 calculation.
Related Calculators
Was this calculator helpful?
Last updated: February 2026
Verified against UK standards · estimates only, confirm with your supplier.