Insulation Thickness Calculator — How Much Insulation Do I Need?
Calculate the insulation thickness needed to meet UK Building Regulations Part L for walls, roofs and floors.
Building Regs default shown. Adjust if needed.
BS EN ISO 6946: wall 0.13, roof 0.10, floor 0.17 (set automatically by element type)
External surface resistance (default 0.04)
Round up thickness to nearest (default 5mm)
Next up: related pages
How We Calculate This
This calculator determines the insulation thickness required to achieve a target U-value for your building element. It uses the standard thermal resistance calculation method from BS EN ISO 6946 and references UK Building Regulations Approved Document L.
The formula
Required insulation R = (1 / target U-value) - Rsi - Rse - existing construction R
Insulation thickness = R × thermal conductivity × 1000 (mm)
For example, to achieve 0.30 W/m²K on a cavity wall (base R = 0.45) with mineral wool (0.035 W/mK): Required R = (1/0.30) - 0.13 - 0.04 - 0.45 = 2.71 m²K/W. Thickness = 2.71 × 0.035 × 1000 = 95mm.
Building Regulations Part L targets (AD L Vol 1, 2021 ed. inc. 2023 amendments)
- External walls: 0.26 W/m²K (new-build limiting, Table 4.1); 0.18 W/m²K (new element in an existing dwelling or extension, Table 4.2); renovation of a retained wall (Table 4.3) — 0.55 by cavity insulation, 0.30 by internal/external insulation
- Roof (all types): 0.16 W/m²K (new-build limiting, Table 4.1 — a single "all roof types" value with no pitched/flat split); 0.15 W/m²K (new element in an existing dwelling or extension, Table 4.2); 0.16 W/m²K (renovation of a retained roof, Table 4.3)
- Ground floor: 0.18 W/m²K (new-build, Table 4.1; new element/extension, Table 4.2); 0.25 W/m²K (renovation of a retained floor, Table 4.3)
The thickness is rounded up to the nearest 5mm to match standard product sizes. Always check manufacturer datasheets for exact lambda values, as these can vary slightly between products.
Frequently Asked Questions
It depends on which Part L target applies. For an existing cavity wall filled by cavity insulation, the AD L 2021 renovation target (Table 4.3) is 0.55 W/m²K — typically met by the standard cavity fill alone. For a wall upgraded by internal or external insulation the renovation target is 0.30 W/m²K, needing roughly 90-100mm of mineral wool or 50-60mm of PIR board. New-build and extension walls must reach the tighter limiting value of 0.26 W/m²K (Table 4.1), and new walls in extensions 0.18 W/m²K (Table 4.2), which need more. Solid walls generally need more insulation than cavity walls, and the exact thickness depends on your existing fabric R-value.
To meet the current UK Building Regulations target of 0.16 W/m²K for a roof, you typically need 270mm of mineral wool insulation at ceiling level. This is usually installed as two layers: 100mm between the joists and 170mm laid across the top at 90 degrees.
PIR (polyisocyanurate) boards like Celotex and Kingspan have a lower thermal conductivity (0.022 W/mK vs 0.035 W/mK for mineral wool), so you need less thickness to achieve the same U-value. However, mineral wool is cheaper per m² and provides better sound insulation. The choice depends on space constraints and budget.
UK Building Regulations Part L 2021 (Approved Document L Volume 1, 2021 edition incorporating 2023 amendments) sets different limiting U-values depending on the work. New dwellings (Table 4.1): walls 0.26 W/m²K, all roof types 0.16 W/m²K (a single roof value, no pitched/flat split), floors 0.18 W/m²K, party walls 0.20 W/m²K, windows 1.6 W/m²K. New thermal elements in an existing dwelling or extension (Table 4.2): walls 0.18 W/m²K, roofs 0.15 W/m²K (a single roof value), floors 0.18 W/m²K, windows 1.4 W/m²K. Renovation of a retained (existing) element (Table 4.3): walls 0.30 W/m²K by internal/external insulation or 0.55 W/m²K by cavity fill, roofs 0.16 W/m²K, floors 0.25 W/m²K. Extensions use the tighter Table 4.2 values, not the renovation ones — always confirm which case applies to your project.
Thermal conductivity (lambda or λ value) measured in W/mK indicates how easily heat passes through a material. Lower values mean better insulation: PIR board is 0.022 W/mK, mineral wool 0.035 W/mK, and brick 0.77 W/mK. Choosing a material with lower conductivity means you need less thickness. See our U-Value Calculator to model full wall build-ups.
Related Guides & Answers
Related Calculators
Was this calculator helpful?
Last updated: February 2026
Verified against UK standards · estimates only, confirm with your supplier.