Ventilation Rates by Room — Part F Reference
Required extract ventilation rates and air changes per hour by room type per Approved Document F (2021). Intermittent and continuous extract rates for UK dwellings.
Intermittent Extract Rates (System 1)
Reference: Approved Document F Volume 1 (2021), Table 1.2.
| Room | Minimum Extract Rate (l/s) | Notes |
|---|---|---|
| Kitchen (adjacent to hob — ducted cooker hood) | 30 | Hood or fan directly above the hob, extracting to outside |
| Kitchen (elsewhere — no hood or recirculating) | 60 | Extract point not adjacent to hob, or recirculating hood |
| Bathroom (with or without WC) | 15 | Operated by light switch with overrun timer |
| WC (separate) | 6 | Operated by light switch with overrun timer |
| Utility room | 30 | If tumble dryer is not externally vented |
Continuous Extract Rates — MEV (System 3)
Reference: Approved Document F Volume 1 (2021), Table 1.3.
| Room | Low Rate (continuous, l/s) | Boost Rate |
|---|---|---|
| Kitchen | 13 | 30 l/s (as intermittent rate) |
| Bathroom | 8 | 15 l/s (as intermittent rate) |
| WC | 6 | 6 l/s |
| Utility room | 8 | 30 l/s (as intermittent rate) |
Whole-Dwelling Ventilation Rates
Reference: Part F Table 1.1. Minimum whole-dwelling ventilation rate.
| Number of Bedrooms | Minimum Whole-Dwelling Rate (l/s) | With 2 Occupants + 1 per Bedroom |
|---|---|---|
| 1 | 19 | 3 occupants assumed |
| 2 | 25 | 4 occupants assumed |
| 3 | 31 | 5 occupants assumed |
| 4 | 37 | 6 occupants assumed |
| 5 | 43 | 7 occupants assumed |
Background Ventilator (Trickle Vent) Requirements
Minimum equivalent area per room (System 1 only). Reference: Part F Table 1.4.
| Room Type | Min Equivalent Area (mm²) |
|---|---|
| Habitable room (incl. kitchen) | 8000 |
| Wet room (bathroom, WC, utility) | 4000 |
Note: These are minimum requirements from Approved Document F Volume 1 (2021 edition). Always refer to the current edition of Approved Document F for definitive requirements. System 2 (passive stack) and System 4 (MVHR) have separate requirements not fully covered here.
Related Pages
See the Part F Ventilation Rates, the Part F Extract Fan Requirements, and the Duct Sizing Tables.
Next up: related pages
Frequently Asked Questions
Approved Document F (2021) specifies minimum extract rates for wet rooms in dwellings. For intermittent extract fans: kitchen 30 l/s (adjacent to hob — ducted cooker hood over hob) or 60 l/s (elsewhere in kitchen — no hood or recirculating), bathroom 15 l/s, WC 6 l/s, utility room 30 l/s. For continuous mechanical extract (MEV): kitchen 13 l/s, bathroom 8 l/s, WC 6 l/s. These are minimum rates and may need to be increased for larger rooms or higher moisture loads.
Intermittent extract fans run when needed (switched on by the occupant, pull cord, or automatic sensor) at a higher flow rate. Continuous extract (MEV — mechanical extract ventilation) runs constantly at a low background rate and boosts to a higher rate when the room is in use. MEV systems are increasingly common in new-build housing as they provide better overall air quality. Part F 2021 accepts either approach as System 1 (background ventilators + intermittent fans) or System 3 (continuous MEV).
Yes. Under System 1 (intermittent extract fans), background ventilation is provided by trickle ventilators in windows and doors. Part F 2021 Table 1.7 requires a minimum equivalent area (EA) of 8000 mm² per habitable room (including kitchens) and 4000 mm² per wet room. Under System 3 (continuous MEV), trickle vents are not required as the MEV system provides continuous air exchange. Under System 4 (MVHR), the building should be relatively airtight and trickle vents are not used.
MVHR (Mechanical Ventilation with Heat Recovery) is System 4 under Part F. It provides supply and extract ventilation through a heat exchanger that recovers 70-95% of the heat from exhaust air. MVHR is most effective in well-sealed buildings (air permeability below 5 m³/hr/m²) and is commonly specified for Passivhaus and high-performance new builds. It is not suitable for leaky older buildings as the recovered heat is negligible compared to losses through the building fabric.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.