Part F Ventilation Rates Reference
Ventilation system strategies and extract rates for dwellings, referencing Approved Document F: Ventilation, Volume 1 - Dwellings (2021 edition, effective 15 June 2022).
Extract Rates — System 1: Intermittent Extract Fans (AD-F 2021 Vol 1, Table 1.1)
| Room | Minimum Extract Rate (l/s) | Notes |
|---|---|---|
| Kitchen (adjacent to hob) | 30 | Cooker hood or extract fan above hob |
| Kitchen (elsewhere) | 60 | Extract fan remote from hob |
| Utility room | 30 | Intermittent extract |
| Bathroom | 15 | With overrun timer (15 mins min) |
| Sanitary accommodation (WC only) | 6 | Intermittent or continuous |
Extract Rates — Systems 3 & 4: Continuous Extract (AD-F 2021 Vol 1, Table 1.2)
| Room | Continuous (Low) Rate (l/s) | Boost Rate |
|---|---|---|
| Kitchen | 13 | 30 l/s (adjacent to hob) |
| Utility room | 8 | 30 l/s |
| Bathroom | 8 | 15 l/s |
| WC (no bath/shower) | 6 | 6 l/s |
Whole Dwelling Ventilation Rate — Systems 3 & 4
The total continuous extract rate for the whole dwelling must be at least the greater of: (a) the sum of individual room rates, or (b) the whole-dwelling minimum based on number of bedrooms.
| Number of Bedrooms | Whole Dwelling Min. Rate (l/s) |
|---|---|
| 1 bedroom | 19 |
| 2 bedrooms | 25 |
| 3 bedrooms | 31 |
| 4 bedrooms | 37 |
| 5+ bedrooms | 43 |
Background Ventilator Sizes — System 1 (AD-F 2021 Vol 1, Table 1.4)
| Bedrooms | Total Equivalent Area (mm²) |
|---|---|
| 1 | 25,000 |
| 2 | 35,000 |
| 3 | 45,000 |
| 4 | 55,000 |
| 5+ | 65,000 |
Purge Ventilation
Every habitable room requires purge ventilation. This is typically achieved by an openable window with a free area of at least 1/20th of the room floor area. Alternatively, a mechanical system capable of achieving 4 air changes per hour (ACH) is acceptable.
Related Calculators
Use the Room Ventilation Calculator for sizing, or the Part F Extract Fan Requirements page for fan sizing and noise limits. See also the Part F Ventilation Calculator.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Next up: related pages
Frequently Asked Questions
System 1 is intermittent extract fans with background ventilators (trickle vents). System 2 is passive stack ventilation (PSV). System 3 is continuous mechanical extract ventilation (MEV). System 4 is continuous mechanical ventilation with heat recovery (MVHR). AD-F Volume 1 (2021 edition) sets out the requirements for each system in its Table 1.1/1.2/1.3 series (Table 1.1 intermittent extract rates, Table 1.2 continuous extract rates, Table 1.3 whole-dwelling rates).
For System 1 (intermittent extract fans), a kitchen requires a minimum of 30 l/s (litres per second) adjacent to the hob (ducted cooker hood over hob), or 60 l/s if located elsewhere in the kitchen (no hood, or a recirculating hood that does not extract outside). For Systems 3 and 4 (continuous extract), the minimum continuous rate is 13 l/s with a boost rate of 30 l/s. These values are from AD-F 2021 Vol 1 Table 1.1.
Purge ventilation provides rapid air exchange to dilute pollutants from decorating, new furniture, or accidental releases. Every habitable room must have purge ventilation capability — typically an openable window with a free area of at least 1/20th of the room floor area. Purge ventilation is required in addition to the normal extract/background ventilation strategy.
For System 1 (intermittent extract with background ventilators), the total equivalent area (EA) of background ventilators depends on the number of bedrooms: 1 bed = 25,000 mm² EA total, 2 bed = 35,000 mm² EA, 3 bed = 45,000 mm² EA, 4 bed = 55,000 mm² EA, 5+ bed = 65,000 mm² EA. These are distributed across habitable rooms and wet rooms per AD-F 2021 Vol 1 Table 1.4.
Scotland has its own ventilation requirements under Technical Handbook Section 3 (Environment) which has broadly similar principles but different specific rates and requirements. Northern Ireland follows Technical Booklet K. The 2021 AD-F update is specific to England; Wales follows its own edition of Approved Document F.