Beam Deflection Limits — Eurocode Reference
Maximum allowable deflection limits for beams and floors per BS EN 1993, BS EN 1995 and Approved Document A. Includes common steel beam section properties.
Deflection Limits by Element Type
Reference: BS EN 1993-1-1 (steel), BS EN 1995-1-1 (timber), BS EN 1992-1-1 (concrete).
| Element | Limit | At 4m Span (mm) | Notes |
|---|---|---|---|
| Floor beams (general) | L/250 | 16 | Total deflection under all loads |
| Floor beams (brittle finishes below) | L/360 | 11.1 | Plasterboard ceiling, tiles, render |
| Roof beams (no brittle finish) | L/200 | 20 | Accessible only for maintenance |
| Roof beams (brittle finish below) | L/250 | 16 | Plastered ceiling below roof |
| Purlins and cladding rails | L/200 | 20 | Metal cladding systems |
| Cantilever beams | L/180 | 22.2 | Cantilever length, not back span |
| Lintels (masonry above) | L/360 | 11.1 | Prevent cracking of masonry and render |
Common Steel Universal Beams (UB) — Section Properties
Reference: BS EN 10365 (formerly BS 4). S275 or S355 grade steel.
| Section | Depth (mm) | Weight (kg/m) | Ixx (cm⁴) | Typical Domestic Use |
|---|---|---|---|---|
| 152 x 89 x 16 UB | 152.4 | 16.0 | 834 | Short lintels, light loads |
| 178 x 102 x 19 UB | 177.8 | 19.0 | 1356 | Lintels, small openings |
| 203 x 133 x 25 UB | 203.2 | 25.1 | 2340 | Floor beams (short spans) |
| 203 x 133 x 30 UB | 206.8 | 30.0 | 2896 | Floor beams, load-bearing lintels |
| 254 x 146 x 31 UB | 251.4 | 31.1 | 4413 | Floor beams, medium spans |
| 254 x 146 x 37 UB | 256.0 | 37.0 | 5537 | Floor beams, heavier loads |
| 305 x 165 x 40 UB | 303.4 | 40.3 | 8503 | Longer spans, wall removal |
| 305 x 165 x 46 UB | 306.6 | 46.1 | 9899 | Heavy floor loads, wide spans |
Quick Deflection Check (Steel UDL)
Formula: deflection (mm) = (5 × w × L⁴) ÷ (384 × E × I)
Where E = 210,000 N/mm² for steel, I in mm⁴ (multiply cm⁴ by 10,000), w in N/mm, L in mm.
Note: These are serviceability limits only. Ultimate strength (bending, shear, buckling) must also be checked. Steel beam design should always be carried out by a structural engineer in accordance with BS EN 1993-1-1 (Eurocode 3). Fire protection requirements per Part B must also be considered for structural steelwork.
Related Pages
See the Joist Span Tables, the Notching and Drilling Rules, and the Steel Beam Calculator.
Next up: related pages
Frequently Asked Questions
L/250 means the maximum allowable deflection is the span length divided by 250. For a 4m beam, L/250 = 4000mm ÷ 250 = 16mm maximum deflection under the full design load. This is a serviceability limit — the beam is not at risk of failure, but greater deflection could cause cracking of finishes, visible sagging, or user discomfort. Different limit values apply depending on the element type and finish materials.
For a domestic floor beam supporting plasterboard ceiling below (a brittle finish), use L/360 to prevent cracking of the ceiling finish. If the ceiling is flexible or there is no ceiling below, L/250 is generally acceptable. For timber floor joists, the TRADA/Eurocode 5 approach limits total deflection to L/250 and also checks that the instantaneous deflection under variable loads does not exceed L/300.
For a simply supported beam with a uniformly distributed load (UDL), deflection = (5 × w × L⁴) ÷ (384 × E × I), where w = load per metre (N/mm), L = span (mm), E = elastic modulus (N/mm²), and I = second moment of area (cm⁴ or mm⁴). For steel, E = 210,000 N/mm². For a point load at mid-span, deflection = (P × L³) ÷ (48 × E × I). These formulae assume ideal simply supported conditions.
Instantaneous deflection occurs immediately when load is applied. Final deflection includes creep — the long-term increase in deflection under sustained load. Creep is significant for timber (kdef factor of 0.6 for service class 1, 0.8 for class 2 per EC5) and concrete but negligible for steel. For timber design, final deflection = instantaneous deflection × (1 + kdef) for permanent loads, plus instantaneous deflection for variable loads.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.