Part E Acoustic Performance Standards
Airborne and impact sound insulation requirements for separating walls and floors, referencing Approved Document E: Resistance to the Passage of Sound (2003 edition incorporating 2004, 2010, 2013, and 2015 amendments).
Minimum Performance Standards (AD-E Table 0.1a & 0.1b)
| Element | Test Parameter | New Build (dB) | Conversion (dB) |
|---|---|---|---|
| Separating wall (airborne) | DnT,w + Ctr | ≥ 45 | ≥ 43 |
| Separating floor (airborne) | DnT,w + Ctr | ≥ 45 | ≥ 43 |
| Separating floor (impact) | L'nT,w | ≤ 62 | ≤ 64 |
| Wall between dwelling and common area (airborne) | DnT,w + Ctr | ≥ 43 | ≥ 43 |
| Floor between dwelling and common area (airborne) | DnT,w + Ctr | ≥ 43 | ≥ 43 |
Internal Walls and Floors Within a Dwelling (AD-E Section 3)
| Element | Requirement |
|---|---|
| Walls between bedrooms and bathrooms/WCs | Good practice guidance only (no statutory minimum) |
| Floors between rooms in dwellings formed by conversion | Rw ≥ 40 dB recommended |
| Walls between rooms and refuse chutes/lifts | See AD-E Section 4 for specific guidance |
Pre-Completion Testing (PCT) Requirements
| Requirement | Detail |
|---|---|
| When required | All new-build dwellings unless using Robust Details |
| Test standard | BS EN ISO 16283 (replaced BS EN ISO 140) |
| Sample rate (first dwelling type) | 1 set of tests per dwelling type per site |
| If test fails | Remedial work required, then re-test |
| Tester accreditation | UKAS-accredited or registered with ANC/ATTMA scheme |
Related Calculators
Use the Sound Insulation Calculator for estimating acoustic performance. See the Part E Sound Reduction page for wall and floor construction specifications.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Next up: related pages
Frequently Asked Questions
New-build separating walls between dwellings must achieve a minimum airborne sound insulation of DnT,w + Ctr >= 45 dB when pre-completion tested. For conversions (material change of use), the target is DnT,w + Ctr >= 43 dB. These values are set out in Table 0.1 of Approved Document E (2003 edition incorporating 2015 amendments).
DnT,w is the weighted standardised level difference measuring airborne sound insulation. The Ctr spectrum adaptation term adjusts for low-frequency sounds (bass, traffic noise). DnT,w + Ctr gives a more realistic single-number rating. Part E specifies DnT,w + Ctr as the performance standard because it better represents real-world complaints like bass music and traffic.
Pre-completion testing (PCT) is required for all new-build dwellings with separating walls or floors, unless the builder uses Robust Details (www.robustdetails.com) which are pre-approved constructions that have been demonstrated to meet Part E without on-site testing. PCT must be carried out by a member of a UKAS-accredited body or registered scheme.
Part E Section 0 deals only with separating elements between dwellings and between dwellings and common areas. Internal walls and floors within a single dwelling have no statutory acoustic requirement under Part E, though good practice is to use similar specifications particularly between bedrooms and noisy rooms.
Scotland has its own acoustic requirements under Technical Handbook Section 5 (Noise), with similar but not identical performance standards. Northern Ireland uses Technical Booklet G which broadly aligns with AD-E. Requirements may vary slightly — always check the relevant jurisdiction's documents.
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.