UK Circuit Breaker Types — MCB, RCD, RCBO
MCB types B, C and D, RCD types A, AC and F, RCBO specifications and ratings from 6A to 63A per BS 7671.
MCB Trip Curves (BS EN 60898)
| Type | Magnetic Trip Range | Application | Examples |
|---|---|---|---|
| B | 3–5 x In | Domestic, commercial lighting | Sockets, lighting, immersion heater |
| C | 5–10 x In | Moderate inrush loads | Fluorescent banks, small motors, UPS |
| D | 10–20 x In | High inrush loads | Welders, transformers, X-ray, compressors |
Common MCB Ratings (Domestic)
| Rating (A) | Type | Typical Circuit | Cable Size |
|---|---|---|---|
| 6 | B | Lighting (single circuit) | 1.0 mm² or 1.5 mm² |
| 10 | B | Lighting (larger circuit) | 1.0 mm² or 1.5 mm² |
| 16 | B | Immersion heater, towel rail | 2.5 mm² |
| 20 | B | Radial socket circuit (small) | 2.5 mm² |
| 32 | B | Ring final circuit (sockets) | 2.5 mm² |
| 40 | B | Cooker circuit (small) | 6.0 mm² |
| 45 | B | Cooker circuit, shower (9.5 kW) | 6.0 mm² or 10 mm² |
| 50 | B | Large shower (10.8 kW+), cooker | 10 mm² |
RCD Types (BS EN 61008 / 61009)
| Type | Detects | Requirement | Application |
|---|---|---|---|
| AC | AC sinusoidal only | Basic (not for all loads) | Simple resistive loads only |
| A | AC + pulsating DC | Minimum for most circuits | Standard domestic circuits |
| F | AC + pulsating DC + high frequency | For VFD/inverter loads | EV chargers, VFD washing machines |
| B | AC + pulsating DC + smooth DC | 3-phase and DC applications | Some EV chargers, 3-phase supplies |
RCD Ratings
| Sensitivity (mA) | Purpose | Application |
|---|---|---|
| 30 | Personal protection (lethal shock) | All socket circuits, bathrooms, outdoor |
| 100 | Fire protection | Fire risk premises, sleeping accommodation |
| 300 | Fire protection | Fire protection on distribution boards |
Related Calculators
See the BS 7671 Circuit Guide for full domestic circuit specifications, or the UK Cable Sizes for cable current ratings. See also the Circuit Breaker Sizing Calculator.
Next up: related pages
Frequently Asked Questions
The letter indicates the magnetic trip characteristic — how much overcurrent causes instant tripping. Type B trips at 3-5 times rated current (best for domestic circuits — lighting, sockets). Type C trips at 5-10 times (used where moderate inrush currents occur — fluorescent lighting, small motors). Type D trips at 10-20 times (used for high inrush loads — welding equipment, transformers, X-ray machines). For domestic installations, Type B is standard for virtually all circuits.
An RCD (Residual Current Device) provides earth leakage protection for a group of circuits but no overcurrent protection. An RCBO (Residual Current Breaker with Overcurrent) combines RCD and MCB protection in a single device — it provides both earth leakage AND overcurrent protection per circuit. RCBOs prevent nuisance tripping affecting multiple circuits, as each circuit has independent protection.
Type AC detects sinusoidal AC earth faults only — it is the basic type but not suitable for all modern loads. Type A also detects pulsating DC faults — this is the minimum requirement for most domestic circuits under BS 7671 18th Edition. Type F adds protection for high-frequency faults from variable speed drives and inverters (e.g. washing machines, air conditioning units with VFDs).
Common causes: a genuine earth fault on an appliance (test by unplugging devices one at a time), moisture in outdoor sockets or junction boxes, deteriorating cable insulation, faulty RCD (they should be tested regularly with the test button), or cumulative leakage from multiple appliances on one RCD circuit. RCBO boards solve the last issue by giving each circuit independent RCD protection.
Related Calculators
Was this calculator helpful?
Last updated: April 2026
Verified against UK standards · estimates only, confirm with your supplier.