Part P & BS 7671 RCD Protection
RCD protection requirements for domestic electrical installations, including circuit types, sensitivity ratings, and notification requirements, referencing Approved Document P: Electrical Safety (2013 edition) and BS 7671:2018+A2:2022 (18th Edition Wiring Regulations).
Circuits Requiring 30 mA RCD Protection (BS 7671:2018+A2:2022)
| Circuit / Location | RCD Required? | Regulation |
|---|---|---|
| All socket outlets ≤ 32 A | Yes — 30 mA | 411.3.3 |
| Bathroom circuits (all zones) | Yes — 30 mA | 701.411.3.3 |
| Circuits supplying mobile equipment outdoors | Yes — 30 mA | 411.3.3 |
| Cables concealed in walls (< 50 mm deep) | Yes — 30 mA (unless in earthed metallic enclosure) | 522.6.202 |
| EV charge point circuits | Yes — 30 mA Type A min. (Type F for some chargers) | 722.531.2 |
| Swimming pool / sauna circuits | Yes — 30 mA | 702/703 |
| Lighting circuits | Recommended (required if cables concealed in walls) | 522.6.202 |
RCD Types and Applications
| RCD Type | Detects | Typical Application |
|---|---|---|
| Type AC | Sinusoidal AC faults only | Not recommended for domestic (legacy) |
| Type A | AC + pulsating DC faults | Standard for most domestic circuits |
| Type F | AC + pulsating DC + mixed frequency | Circuits with inverter drives, some EV chargers |
| Type B | All fault types inc. smooth DC | Industrial, PV systems, some EV chargers |
Part P Notification Requirements (England)
| Work Type | Notifiable? | Route |
|---|---|---|
| New circuit installation | Yes | Building Control or competent person scheme |
| Consumer unit replacement | Yes | Building Control or competent person scheme |
| Alteration to existing circuit in special location (bath/shower room) | Yes | Building Control or competent person scheme |
| Work in kitchens (not also bath/shower room) | No (since AD P 2013) | Kitchen alone is not a special location |
| Outdoor electrical work (garden, lighting) — existing circuit alteration | No (since AD P 2013) | Outdoor is no longer a special location |
| New circuit outdoors (e.g. EV charger, outbuilding) | Yes (new circuit rule) | Building Control or competent person scheme |
| Replacing socket outlets, switches, light fittings | No | N/A |
| Adding a fused spur to existing circuit (not in bath/shower room) | No | N/A |
| Like-for-like replacement of accessories | No | N/A |
Scotland & Northern Ireland
Scotland does not have a direct equivalent of Part P — electrical work in dwellings is covered under Technical Handbook Section 4.5 (Electrical safety) and compliance with BS 7671 is required. Northern Ireland requires compliance with BS 7671 through Technical Booklet P (Electrical safety) and notifiable electrical work follows a similar but separate scheme. BS 7671 applies across all UK jurisdictions.
Related Calculators
Use the Cable Sizing Calculator for circuit design, or the BS 7671 Circuit Guide for domestic circuit specifications. See also the Part P Notification Calculator.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Next up: related pages
Frequently Asked Questions
Under BS 7671:2018+A2:2022 (Regulation 411.3.3 and 411.3.4), 30 mA RCD protection is required for: all socket outlet circuits rated up to 32 A, all circuits in bathrooms (Zone 0-2 and beyond), circuits supplying mobile equipment outdoors, circuits in locations with increased shock risk, and cables concealed in walls at a depth less than 50 mm (unless in an earthed metallic enclosure or protected by 30 mA RCD).
Type AC detects sinusoidal AC fault currents only. Type A detects AC and pulsating DC faults (required for most domestic circuits under BS 7671). Type F detects AC, pulsating DC, and composite faults from frequency-controlled equipment (e.g. inverter drives, EV chargers). Type B detects all fault types including smooth DC. BS 7671 generally requires Type A as a minimum for domestic installations.
In England, AD P 2013 (still current) notifiable electrical work is limited to three categories: (a) installation of a new circuit; (b) replacement of a consumer unit; (c) any addition or alteration to existing circuits in a "special location" — which AD P defines as rooms containing a bath or shower, and swimming pool/sauna rooms. Since 2013, kitchens and outdoor areas are NO LONGER special locations (unless they overlap with a bath/shower room). Work in kitchens or gardens that does not involve a new circuit or CU replacement is not in itself notifiable. Notifiable work must be either inspected by Building Control or carried out by a competent person registered with a scheme (e.g. NICEIC, NAPIT, ELECSA).
No. A 30 mA RCD provides additional protection against electric shock but is not a substitute for basic protection (insulation of live parts) and fault protection (earthing and overcurrent devices). An RCD detects earth leakage current — it will not operate if a person touches live and neutral simultaneously without any current flowing to earth. RCDs are a supplementary measure per BS 7671 Chapter 41.