TradeCalculator.co.uk
EV Charger Cable Sizing Calculator — BS 7671 Section 722
Size cables correctly for electric vehicle charger installations. Checks current capacity and voltage drop per BS 7671 18th Edition and IET Code of Practice for EV Charging.
Total cable route distance from consumer unit to charger
UK nominal supply voltage (default 230V)
BS 7671 limit for power circuits (default 11.5V = 5%)
Combined derating Ca×Cg×Ci. IET CoP EV example uses 0.75 (cable touching thermal insulation one side). Set 1.0 for reference conditions.
Safety notice
Electrical work in dwellings can be notifiable under Part P of the Building Regulations. Treat these figures as planning guidance only: circuits must be designed, installed and certified to BS 7671 by a competent person, normally a registered electrician.
Next up: related pages
How We Calculate This
This calculator sizes the cable for an EV charger installation based on BS 7671 18th Edition Section 722 and the IET Code of Practice for Electric Vehicle Charging Equipment Installation. It checks both current carrying capacity and voltage drop.
The sizing process
Step 1 — Design current. EV charging is a continuousload (BS 7671 Reg 722.311), so the circuit is sized at 100% of the charger output with no diversity. A 7kW charger is protected by a 32A device, so the design current is taken as Ib = 32A (not the back-calculated 7000 ÷ 230 = 30.4A, which would undersize the circuit). A 3.6kW charger uses 16A; a 22kW three-phase charger uses 32A per phase.
Step 2 — Current capacity (Reg 433.1.1).Coordinate Ib ≤ In ≤ Iz: the cable’s current-carrying capacity Iz must be ≥ the protective-device rating In (32A), not merely the design current. Allowing for derating, the required tabulatedcapacity is It ≥ In ÷ Cf. With the IET Code of Practice rating factor Cf = 0.75 (cable in contact with thermal insulation on one side), It ≥ 32 ÷ 0.75 = 42.7A, which rules out 4mm² (37A) and selects 6mm² (47A) for a typical 7kW charger.
Step 3 — Voltage drop.VD = (mV/A/m × current × length) ÷ 1000. Must not exceed 11.5V (5% of 230V) single-phase, or 20V (5% of 400V) three-phase.
The calculator’s capacities are BS 7671 values for flat twin & earth at 30°C ambient on a single circuit. Clipped-direct ratings come from Table 4D5 (Reference Method C). Conduit and trunking ratings come from Table 4D2A (Reference Method B, one two-core cable, single phase), because Table 4D5 tabulates no conduit or trunking column at all: it carries only the thermal-insulation methods, Method A and Method C. Using 4D2A here is standard practice and is the conservative choice. For grouped circuits, higher ambient or thermal insulation, lower the rating factor to derate; for a 22kW three-phase charger use 4-core SWA and confirm its capacity against the armoured tables.
Where this calculator stops
Table 4D5 runs from 1mm² to 16mm², which is the whole range flat twin and earth is manufactured in. If a long run or a heavy derating pushes the circuit past 16mm², the calculator refuses instead of naming a bigger twin and earth: no such cable exists to buy, and no published table supports a rating for one. A circuit that big belongs on armoured cable rated from Table 4D4A and designed by a qualified electrician.
Buried runs are refused for the same reason. Table 4D5 has no direct-burial column because flat twin and earth is not rated for burial. An underground route to a driveway or detached garage needs armoured cable, laid at the correct depth with marker tape, sized against the armoured tables.
EV-specific requirements (Section 722)
- Dedicated circuit: EV charger must be on its own dedicated circuit from the consumer unit
- RCD protection: 30mA, Type A minimum (Type B if no built-in DC protection)
- PME earthing: Risk assessment required. TT earthing may be needed for outdoor chargers
- Load management: May be required if supply capacity is limited (smart chargers can reduce output)
- Cable type: SWA for outdoor/buried runs, twin & earth for internal clipped routes
Always consult a qualified electrician (Part P registered) for EV charger installations. The installer must notify Building Control and provide an Electrical Installation Certificate.
Working figures for this are collected in our Part S EV Charging Requirements reference table.
Frequently Asked Questions
A 7kW (32A) EV charger typically requires 6mm² SWA or twin & earth cable for runs up to about 25m. For longer runs, 10mm² cable may be needed to keep voltage drop within the 5% limit (11.5V on 230V). The cable must be protected by a 32A Type B MCB with Type A (minimum) or Type B RCD at 30mA. Use our Cable Sizing Calculator to verify the correct cable size for your installation method.
SWA (Steel Wire Armoured) cable is recommended for outdoor cable runs and is required for buried cables. If the cable route is entirely indoors (e.g., consumer unit to garage wall), twin and earth may be acceptable if clipped and protected. For any underground route (e.g., to a driveway), SWA buried at minimum 500mm depth with cable marker tape is required.
Most UK homes have PME (Protective Multiple Earthing / TN-C-S) supplies. BS 7671 Section 722 requires a risk assessment for EV chargers on PME supplies because a fault on the supply PEN conductor could put dangerous voltages on the charger's metalwork. Solutions include: using a TT earth electrode, installing a charger with PEN fault protection, or using an EVCP (EV Charging Point) with built-in PEN fault detection.
Most UK homes have a single-phase supply, so a 22kW three-phase charger is not possible without a supply upgrade from the DNO. Single-phase homes are limited to 7kW (32A) maximum for AC charging. If you have a three-phase supply (common in some rural areas and larger properties), a 22kW charger is possible but requires a dedicated three-phase circuit with appropriate cable sizing.
Per BS 7671 Section 722, an EV charger requires 30mA RCD protection. The minimum RCD type is Type A — which detects pulsating DC fault currents. If the charger does not have built-in 6mA DC protection, a Type B RCD is required. Most modern smart chargers (Zappi, PodPoint, Ohme) include built-in DC protection, allowing a Type A RCD or RCBO. See our RCD Selection Guide for help choosing the right RCD type.
Related Calculators
Was this calculator helpful?
Last updated: February 2026
Verified against UK standards · estimates only, confirm with your supplier.