Part S EV Charging Requirements
Electric vehicle charge point requirements for new buildings and major renovations, referencing Approved Document S: Infrastructure for the Charging of Electric Vehicles (2021 edition, effective 15 June 2022).
Residential Requirements (AD-S Section 1)
| Building Type | Charge Points Required | Cable Routes |
|---|---|---|
| New dwelling with parking | 1 per dwelling | Recommended for additional spaces |
| Block of flats (parking = dwellings) | 1 per dwelling with parking space | Cable route to each remaining space |
| Block of flats (parking < dwellings) | 1 per parking space | N/A (all spaces have charge points) |
| Material change of use (with parking) | 1 per dwelling with parking space | Cable route to each remaining space |
Non-Residential Requirements (AD-S Section 2)
| Building Type | Charge Points Required | Cable Routes |
|---|---|---|
| New build (> 10 spaces) | 1 charge point | Cable route to 1 in 5 of remaining spaces |
| Major renovation (> 10 spaces) | 1 charge point | Cable route to 1 in 5 of remaining spaces |
| ≤ 10 spaces | No requirement | No requirement |
Charge Point Specifications (AD-S)
| Specification | Requirement |
|---|---|
| Minimum power output | 7 kW |
| Charging mode | Mode 3 (dedicated EV charging with control and protection) |
| Connector type | Type 2 (BS EN 62196-2) — untethered socket or tethered cable |
| Smart charging | Must be smart (capable of responding to signals to shift demand) |
| Electrical supply | Single-phase 32 A (typical 7 kW) or three-phase (22 kW) |
| RCD protection | 30 mA Type A minimum (Type F or B for some chargers) |
| Installation standard | IET Code of Practice for Electric Vehicle Charging Equipment Installation (4th edition) |
Cable Route Requirements
| Requirement | Detail |
|---|---|
| What is a cable route? | A continuous route for cables from the consumer unit to the parking space — ducts, trunking, or containment |
| Capacity | Must accommodate the cable for a 7 kW charge point (6 mm² minimum) |
| Distribution board | Spare way(s) must be provided for future charge point connection |
| Earthing | PME earthing restrictions may apply — check BS 7671 and IET CoP |
Worked Examples
| Scenario | Charge Points | Cable Routes |
|---|---|---|
| New house with driveway (2 spaces) | 1 | Recommended to 2nd space |
| Block of 20 flats, 15 parking spaces | 15 | 0 (all spaces have charge points) |
| Office with 30 parking spaces | 1 | 6 (1/5 of 29 remaining, rounded up) |
| Retail with 8 parking spaces | 0 (≤ 10 spaces) | 0 |
Related Calculators
Use the Cable Sizing Calculator for EV circuit design, or the Part P RCD Requirements for electrical safety guidance. See also the EV Charger Cable Sizing Calculator.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Next up: related pages
Frequently Asked Questions
Part S (Approved Document S, 2021 edition, effective 15 June 2022 in England) applies to: new residential buildings with associated parking, new non-residential buildings with more than 10 parking spaces, residential buildings undergoing a material change of use with associated parking, and non-residential buildings undergoing major renovation with more than 10 spaces. It does not apply to existing buildings without a change of use or major renovation.
Each new dwelling with associated parking must have one charge point. If a dwelling has more than one parking space, only one charge point is required (cable routes to additional spaces are recommended but not mandatory). The charge point must be a minimum 7 kW Mode 3 (Type 2 connector) and comply with BS EN 61851 and IET Code of Practice for Electric Vehicle Charging Equipment Installation.
For new residential buildings with more than one dwelling (e.g. a block of flats), at least one charge point is required for each dwelling that has an associated parking space. Where there are fewer parking spaces than dwellings, one charge point per space is required. Cable routes must be provided for any additional parking spaces not fitted with a charge point.
New non-residential buildings with more than 10 parking spaces must have at least one charge point, plus cable routes to one-fifth of the remaining spaces. For example, a building with 50 spaces needs 1 charge point and cable routes to 10 spaces (one-fifth of the remaining 49, rounded up). This is per AD-S Section 2.
Part S applies in England only. Wales has its own edition with similar requirements. Scotland amended its Technical Handbook (Section 4, Safety) to include EV charging requirements. Northern Ireland does not yet have equivalent building regulations but may introduce them. The IET Code of Practice for EV Charging Equipment Installation applies UK-wide.