Extract Fan Sizing Calculator — Kitchens, Bathrooms & WCs
Size extract fans for domestic rooms per Approved Document F (2021). Calculates required flow rates, fan size, and duct diameter for kitchens, bathrooms, and utility rooms.
No openable window → ADF 2021 para 1.51 needs a 15-min overrun timer
No external walls (internal room) → ADF 2021 para 1.48 sets a 4 ACH purge minimum
Total duct length from fan to outside
Indicative ~2.5 Pa per 90° bend; check the actual fitting's resistance chart
Min 15 min required where there is no openable window (ADF para 1.51); good practice otherwise
Next up: related pages
How We Calculate This
This calculator sizes extract fans for domestic rooms using the minimum extract rates specified in Approved Document F (2021 edition) Tables 1.1 and 1.2. These rates are the legal minimum for new dwellings and major renovations in England and Wales.
How it works
The calculator looks up the minimum intermittent and continuous extract rates for your room type and then recommends an appropriate fan size and duct diameter. The regulations set two separate, independent conditions for wet rooms. Approved Document F 2021 para 1.48 applies where a wet room has no external walls (an internal room): the intermittent fan must extract at least four air changes per hour to meet the purge ventilation standard, so the calculator uses the greater of this and the Table 1.1 minimum. Separately, para 1.51 applies where a room has no openable window: the fan must keep running for at least 15 minutes after the room is vacated (overrun timer). A room can meet one condition without the other — an internal room with no external walls triggers the 4 ACH purge rule whether or not it has a window, while a room with an external wall but no openable window needs only the overrun. There is no across-the-board percentage uplift for internal rooms in the regulations.
Duct pressure estimation (indicative)
The static pressure the fan must overcome is estimated from the duct length, number of bends, and grille resistance, to indicate whether an axial fan (low pressure) or centrifugal/in-line fan (higher pressure) is needed. The figure is an indicative ballpark, not a regulatory value: it assumes roughly 1–1.5 Pa/m for smooth duct, about 2.5 Pa per 90° bend and around 10 Pa for grilles. Flexible duct can be three to four times more resistive (~3–4 Pa/m), so always size the fan against the manufacturer’s resistance chart for your actual duct.
ADF 2021 Tables 1.1 and 1.2 rates
- Kitchen: 30 l/s intermittent where a cooker hood extracts to outside, 60 l/s where there is no hood or it does not extract outside (e.g. recirculating), 13 l/s continuous high rate
- Bathroom / Shower: 15 l/s intermittent (8 l/s continuous high rate); 15-min overrun required if no openable window (para 1.51)
- WC (sanitary accommodation): 6 l/s intermittent and continuous; 15-min overrun required if no openable window (para 1.51)
- Utility: 30 l/s intermittent (8 l/s continuous high rate)
Working figures for this are collected in our Part F Extract Fan Requirements reference table.
Frequently Asked Questions
Per Approved Document F (2021) Tables 1.1 and 1.2, a bathroom requires a minimum intermittent extract rate of 15 l/s (or 8 l/s if using continuous mechanical extract). A standard 100mm axial fan rated at 15+ l/s will meet the intermittent requirement for most domestic bathrooms. Where the room has no openable window, the fan must also have a 15-minute overrun timer (ADF 2021 para 1.51); with an openable window the overrun is good practice but not mandatory. For larger bathrooms or those with long duct runs, a centrifugal/in-line fan may be needed to overcome duct resistance.
Under current Building Regulations (Approved Document F 2021), bathrooms (with a bath or shower) are wet rooms that require dedicated extract ventilation. For new builds and major renovations, Part F is met by natural ventilation with background ventilators plus an intermittent extract fan, continuous mechanical extract ventilation, or mechanical ventilation with heat recovery (the three system types in ADF 2021 Table 1.6). An openable window provides purge ventilation but does not on its own replace the required wet-room extract fan.
Approved Document F 2021 Table 1.1 specifies 30 l/s minimum intermittent extract where a cooker hood extracts to the outside, or 60 l/s where there is no cooker hood or the hood does not extract to the outside (e.g. a recirculating hood). If using continuous mechanical extract (MEV/dMEV), Table 1.2 sets a 13 l/s high rate for kitchens. The intermittent rate applies when the fan is switched on during cooking, while continuous runs at a low background rate at all times.
Axial fans are cheaper and simpler but cannot overcome much duct resistance — they are suitable for wall-mounted installations with short, straight duct runs (under 1.5m). Centrifugal or in-line fans generate much higher static pressure and should be used for longer duct runs, multiple bends, or roof-mounted terminals. As a rule: if the total duct run exceeds 3m or has more than 2 bends, use a centrifugal fan.
Approved Document F 2021 (para 1.51) requires a 15-minute overrun specifically where a room has no openable window: the intermittent extract fan must keep running for at least 15 minutes after the room is vacated, to clear residual moisture. A bathroom, shower room or WC that does have an openable window is not obliged to have an overrun timer, though fitting one is good practice. Kitchen extract fans do not require an overrun timer — they are typically manually controlled or linked to a humidistat. Note also para 1.48: a wet room with no external walls must extract at four air changes per hour to meet the purge standard.