Part F Ventilation Calculator — Extract Rates & Trickle Vents

Calculate Part F ventilation requirements: extract rates by room type, whole building ventilation rate, trickle vent sizes and system selection (MEV/dMEV/MVHR).

How We Calculate This

This calculator determines ventilation requirements per Approved Document F for UK dwellings.

Extract rates (ADF 2021 Vol 1 Table 5.1a)

Kitchen: 30 l/s intermittent (adjacent to hob, or 60 l/s elsewhere) or 13 l/s continuous. Bathroom/en-suite: 15 l/s intermittent or 8 l/s continuous. Utility: 30 l/s intermittent or 8 l/s continuous. WC: 6 l/s.

Whole building rate

The greater of 0.3 l/s per m2 floor area or 8 l/s per occupant.