Part B Unprotected Areas & Boundary Distance
Boundary distance calculations and permitted unprotected areas for external walls, referencing Approved Document B: Volume 1 - Dwellings and Volume 2 - Buildings other than dwellings (2019 edition incorporating 2020 amendments), Diagram 40 and Table 14.
Method 1 — Permitted Unprotected Areas for Dwellings (AD-B Vol 1, Table 14 / Diagram 40)
For residential buildings not more than 3 storeys, the maximum total unprotected area on any side depends on the minimum distance from the side of the building to the relevant boundary.
| Min. Distance to Boundary | Max. Unprotected Area (m²) | Notes |
|---|---|---|
| Less than 1 m | None (fire-rated wall required) | Small openings up to 0.1 m² permitted at 1.5 m spacing |
| 1 m | 5.6 m² | Typical for terraced/semi-detached side walls |
| 2 m | 12 m² | Common for detached houses |
| 5 m | 40 m² | Most windows achievable |
| 6 m | No limit | Wall can be fully unprotected |
| More than 6 m | No limit | No restriction on unprotected areas |
Key Rules for Boundary Distance Assessment
| Rule | Requirement |
|---|---|
| Relevant boundary | The boundary of the land, or the centre line of a road/railway/canal adjoining the site |
| Measurement | Perpendicular from the external wall face to the relevant boundary |
| Combustible cladding | Counts as unprotected area in most circumstances |
| Small openings | Openings ≤ 0.1 m² each (e.g. airbricks) may be disregarded if spaced ≥ 1.5 m apart |
| Portal frame buildings | Special rules apply — see AD-B Vol 2 Section 14 |
Methods Summary (AD-B Section 13/14)
| Method | Approach | Typical Use |
|---|---|---|
| Method 1 | Simple table lookup (Diagram 40 / Table 14) | Houses and small residential up to 3 storeys |
| Method 2 | Enclosing rectangle (BRE 187) | Larger buildings, non-residential |
| Method 3 | Aggregate notional area with weighted zones | Complex facades with mixed materials |
| Method 4 | Fire engineering (BS 9999 or equivalent) | Complex or unusual buildings |
Related Calculators
Use the External Fire Spread Calculator to check unprotected areas against boundary distance. See the Part B Fire Resistance Ratings page for fire rating requirements by element.
Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.
Next up: related pages
Frequently Asked Questions
An unprotected area is any part of an external wall that does not achieve the required fire resistance. This includes windows, doors, combustible cladding, and any opening or non-fire-rated section. The permitted total unprotected area depends on the distance to the relevant boundary, calculated using methods in AD-B Section 13 (dwellings) and Section 14 (other buildings).
If a wall is 1 metre or more from the relevant boundary, some unprotected areas are permitted. At exactly 1 m from the boundary, dwellings up to 3 storeys may have up to 5.6 m² of unprotected area per side (per Diagram 40 / Table 14). At less than 1 m from the boundary, walls must generally be fire-rated with no unprotected areas unless they are very small (less than 1 m² in total).
Method 1 (Diagram 40) is the simplified method for small residential buildings. Method 2 uses the "enclosing rectangle" approach from BRE Report BR 187. Method 3 is the "aggregate notional area" method allowing trade-offs between different parts of the facade. Method 4 uses BS 9999 or other fire engineering approaches for complex buildings. Most domestic work uses Method 1.
Yes. If a conservatory or extension is within the relevant boundary distance, its glazing and any non-fire-rated walls count as unprotected areas. Where a conservatory is built against a boundary wall, the existing wall must maintain its fire resistance, and the conservatory walls facing the boundary must be fire-rated or set back sufficiently.
Scotland uses Technical Handbook Section 2.6 (Spread to neighbouring buildings) which follows similar principles but with different tables. Northern Ireland uses Technical Booklet E with boundary distance requirements broadly aligned to AD-B. Always refer to the relevant jurisdiction's documents for exact requirements.