Part B Fire Resistance Ratings Reference
Minimum periods of fire resistance read cell by cell from Table B2, the element provisions from Table B1 and the fire doorset provisions from Table C1 of Approved Document B Volume 1 (2019 edition incorporating the 2020, 2022 and 2025 amendments, collated with the 2026 and 2029 amendments), with the table row and note number beside every figure.
Minimum Periods of Fire Resistance (AD B Appendix B, Table B2)
Table B2 is the only table in Approved Document B that sets minimum periods of fire resistance for elements of structure, and it is identical in Volume 1 (Dwellings) and Volume 2 (Buildings other than dwellings). You read it by purpose group down the side, then by the height of the top floor above ground across the top, with two further columns read on the depth of the lowest basement. The version below carries the banner “Effective until 1 September 2029”, so it is the in-force version.
Two headings that are easy to misread. The height columns are the height of the top floor above ground in a building or separated part of a building, not the number of storeys, and the notes state that for single storey buildings the periods under the heading “Up to 5” apply. Purpose group 1(a) is the block of flats; the dwellinghouse is 1(b) and 1(c). Getting those two the wrong way round changes almost every figure in the row.
| Purpose group (Table B2 row) | Basement more than 10 m deep | Basement up to 10 m | Top floor up to 5 m | Up to 11 m | Up to 18 m | Up to 30 m | More than 30 m |
|---|---|---|---|---|---|---|---|
| 1(a) Block of flats, without sprinkler system | 90 | 60 | 30 † | 60 + § | Not permitted (2) | Not permitted (2) | Not permitted (2) |
| 1(a) Block of flats, with sprinkler system (3) | 90 | 60 | 30 † | 60 + § | 60 + § | 90 + | 120 + |
| 1(b) and 1(c) Dwellinghouse | Not applicable (4) | 30 * † | 30 † | 60 (5) | 60 (5) | Not applicable (4) | Not applicable (4) |
| 2(a) Residential: institutional | 90 | 60 | 30 † | 60 | 60 | 90 | 120 ‡ |
| 2(b) Residential: other | 90 | 60 | 30 † | 60 | 60 | 90 | 120 ‡ |
| 3 Office, without sprinkler system | 90 | 60 | 30 † | 60 | 60 | 90 | Not permitted (6) |
| 3 Office, with sprinkler system (3) | 60 | 60 | 30 † | 30 † | 30 † | 60 | 120 ‡ |
| 4 Shop and commercial, without sprinkler system | 90 | 60 | 60 | 60 | 60 | 90 | Not permitted (6) |
| 4 Shop and commercial, with sprinkler system (3) | 60 | 60 | 30 † | 60 | 60 | 60 | 120 ‡ |
| 5 Assembly and recreation, without sprinkler system | 90 | 60 | 60 | 60 | 60 | 90 | Not permitted (6) |
| 5 Assembly and recreation, with sprinkler system (3) | 60 | 60 | 30 † | 60 | 60 | 60 | 120 ‡ |
| 6 Industrial, without sprinkler system | 120 | 90 | 60 | 90 | 90 | 120 | Not permitted (6) |
| 6 Industrial, with sprinkler system (3) | 90 | 60 | 30 † | 60 | 60 | 90 | 120 ‡ |
| 7(a) Storage and other non-residential, without sprinkler system | 120 | 90 | 60 | 90 | 90 | 120 | Not permitted (6) |
| 7(a) Storage and other non-residential, with sprinkler system (3) | 90 | 60 | 30 † | 60 | 60 | 90 | 120 ‡ |
| 7(b)(i) Open sided car park for light vehicles (7) | Not applicable | Not applicable | 15 † # | 15 † # (8) | 15 † # (8) | 15 † # (8) | 60 |
| 7(b)(ii) Any other car park for light vehicles | 90 | 60 | 30 † | 60 | 60 | 90 | 120 ‡ |
All figures are minutes. The purpose group name in the first column is the name Table B2 itself gives the row. Where a row is split into a “without sprinkler system” and a “with sprinkler system” line, both lines are shown, because reading the wrong one is the commonest way to arrive at a period that is too short: a block of flats above 11m has no unsprinklered line at all.
The Table B2 Notes That Change the Figure
The symbols and numbers in the cells above are not decoration. Several of them move the period, and two of them remove it. These are quoted from the notes printed under Table B2.
| Marker | What the note says |
|---|---|
| (no marker) | “For single storey buildings, the periods under the heading ‘Up to 5’ apply. If single storey buildings have basements, for the basement storeys the period appropriate to their depth applies.” |
| * | “For the floor over a basement or, if there is more than one basement, the floor over the topmost basement, the higher of the period for the basement storey and the period for the ground or upper storey applies.” |
| † | “For compartment walls that separate buildings, the period is increased to a minimum of 60 minutes.” This is about walls between separate buildings and it applies to every purpose group carrying the marker. It is not a 60 minute floor for flats. |
| + | “For any floor that does not contribute to the support of the building within a flat of more than one storey, the period is reduced to 30 minutes.” |
| § | “For flat conversions, refer to paragraphs 6.5 to 6.7 regarding the acceptability of 30 minutes.” |
| ‡ | “For elements that do not form part of the structural frame, the period is reduced to 90 minutes.” |
| # | “For elements that protect the means of escape, the period is increased to 30 minutes.” |
| 1 | “Refer to note 1, Table B1 for the specific provisions of test.” |
| 2 | “Blocks of flats with a top storey more than 11m above ground level (see Diagram D6) should be fitted with a sprinkler system in accordance with Appendix E.” The note adds that sprinklers should be provided within the individual flats and do not need to be provided in common areas such as stairs, corridors or landings when those areas are fire sterile. |
| 3 | “‘With sprinkler system’ means that the building is fitted throughout with an automatic sprinkler system in accordance with Appendix E.” |
| 4 | “Very large (with a top storey more than 18m above ground level or with a 10m deep basement) or unusual dwellinghouses are outside the scope of the guidance provided with regard to dwellinghouses.” |
| 5 | “A minimum of 30 minutes in the case of three storey dwellinghouses, increased to 60 minutes minimum for compartment walls separating buildings.” |
| 6 | “Buildings within the ‘office’, ‘shop and commercial’, ‘assembly and recreation’, ‘industrial’ and ‘storage and other non-residential’ (except car parks for light vehicles) purpose groups (purpose groups 3 to 7(a)) require sprinklers where there is a top storey more than 30m above ground level.” |
| 7 | “The car park should comply with the relevant provisions in the guidance on requirement B3, Section 11 of Approved Document B Volume 2.” |
| 8 | Certain steel elements are deemed to satisfy the 15 minute minimum when tested to the European test method: beams supporting concrete floors at a maximum Hp/A of 230 m-1, free-standing columns at a maximum 180 m-1 and wind bracing and struts at a maximum 210 m-1, all under full design load. Guidance is also available in BS EN 1993-1-2. |
Note 5 is the one most often skipped. The dwellinghouse cells at “Up to 11” and “Up to 18” print 60 minutes, but note 5 relaxes that to a minimum of 30 minutes for three storey dwellinghouses, holding 60 minutes only for compartment walls separating buildings. Note 5 is attached to those two cells and nowhere else.
Why a House Above 18 m Has No Period
Table B2 rows 1(b) and 1(c) print Not applicable, not a number, in the “Up to 30” column, the “More than 30” column and the basement column for a lowest basement more than 10m deep. Note 4 gives the reason: a very large dwellinghouse, meaning one with a top storey more than 18m above ground level or with a 10m deep basement, and an unusual dwellinghouse, are outside the scope of the guidance provided with regard to dwellinghouses.
There is therefore no Approved Document period for that building, and any figure presented as one has been invented. Take the design to a fire engineer, normally working to BS 9991, and agree the strategy with your building control body. Note that a tall block of flatsis a different purpose group, 1(a), and does have figures: 90 minutes at “Up to 30” and 120 minutes at “More than 30”, both on the sprinklered line, because note 2 makes sprinklers mandatory in a block of flats with a top storey more than 11m above ground level.
Fire Resistance by Element (AD B Appendix B, Table B1)
Table B1 says which criteria each element has to meet and for how long. Most rows point back at Table B2 for the period; the rows that carry their own number do not scale with the height of the building. The letters are defined in Table B1 note 1: R is loadbearing capacity, E is integrity, I is insulation.
| Item | Part of building | Minimum provision, European classification | Type of exposure |
|---|---|---|---|
| 1 | Structural frame, beam or column | R, see Table B2 | Exposed faces |
| 2 | Loadbearing wall. For a wall also described in any of the following items, the more onerous guidance should be applied | R, see Table B2 | Each side separately |
| 3(a) | Floor between a shop and a flat above | REI 60 or see Table B2, whichever is greater | From underside |
| 3(b) | Floor in the upper storey of a two storey dwellinghouse, but not over a garage or basement | R 30 and EI 15 | From underside |
| 3(c) | Any other floor, including compartment floors | REI, see Table B2 | From underside |
| 4(a) | Any part of a roof forming an escape route | REI 30 | From underside |
| 4(b) | Any roof that performs the function of a floor | REI, see Table B2 | From underside |
| 5(a) | External wall, any part a maximum of 1000 mm from any point on the relevant boundary | REI, see Table B2 | Each side separately |
| 5(b) | External wall, any part a minimum of 1000 mm from the relevant boundary | RE see Table B2, and I 15 | From inside the building |
| 5(c) | External wall, any part beside an external escape route | RE 30 | From inside the building |
| 6(a) | Compartment wall separating a flat from any other part of the building (para 7.1) | REI 60 or see Table B2, whichever is less | Each side separately |
| 6(b) | Compartment wall separating occupancies | REI 60 or see Table B2, whichever is less | Each side separately |
| 7 | Compartment walls other than in item 6 or item 10 | REI, see Table B2 | Each side separately |
| 8(a) | Protected shaft, excluding any firefighting shaft: any glazing described in Section 7 Diagram 7.2 | E 30 | Each side separately |
| 8(b) | Any other part between the shaft and a protected lobby or corridor described in Section 7 Diagram 7.2 | REI 30 | Each side separately |
| 8(c) | Any part of a protected shaft not described in 8(a) or 8(b) | REI, see Table B2 | Each side separately |
| 9(a) | Enclosure to a protected stairway, where it does not form part of a compartment wall or a protected shaft | REI 30 | Each side separately |
| 9(b) | Enclosure to a lift shaft, on the same condition | REI 30 | Each side separately |
| 10 | Wall or floor separating an attached or integral garage from a dwellinghouse | REI 30 | From garage side |
| 11 | Fire resisting construction in dwellinghouses not described elsewhere | REI 30 | Each side separately |
| 12 | Firefighting shafts | REI 120 | From side remote from shaft |
| 12(a) | Construction separating a firefighting shaft from the rest of the building | REI 60 | From shaft side |
| 12(b) | Construction separating firefighting stair, firefighting lift shaft and firefighting lobby | REI 60 | Each side separately |
| 13(a) | Enclosure to a protected lobby, where it is not a compartment wall or described in item 8 | REI 30 | Each side separately |
| 13(b) | Enclosure to a protected corridor, on the same condition | REI 30 | Each side separately |
| 14 | Sub-division of a corridor | REI 30 | Each side separately |
Three rows are worth reading twice. Item 9(a) fixes the enclosure to a protected stairway at REI 30, and it does not rise with the height of the building; where those same walls are also a compartment wall or a protected shaft, items 6, 7 or 8 apply instead and those do point at Table B2. Item 6(a) is a cap and not a floor: a compartment wall separating a flat from any other part of the building is REI 60 or Table B2, whichever is less, so in a block of flats with a top floor up to 5m it is REI 30, because Table B2 gives 30 there. And item 3(b) gives the upper floor of a two storey dwellinghouse R 30 and EI 15, which is a lower insulation period than the REI 30 usually assumed.
Table B1 note 1 also warns that the national BS 476 classifications do not automatically equate with the European classifications, so a product cannot be assumed to hold a European class unless it has been tested to it. Para B23 names the three tables and what each one does: “Table B1 gives the specific requirements for each element of structure. Table B2 sets out the minimum periods of fire resistance for elements of structure. Table B3 sets out limitations on the use of uninsulated fire resisting glazed elements.” So Table B3 exists, but it is the glazing table on escape routes, not a table of periods, and there is no Table A1 or Table A2 in this edition at all: Appendix A is Key terms. The Table A2 numbering belongs to the 2006 and 2013 editions and Table B4 to the 2019 edition incorporating the 2020 and 2022 amendments.
Fire Doorset Provisions (AD B Appendix C, Table C1)
Doorset ratings come from Table C1, not from the period of the surrounding construction, so they are frequently a different number from the wall the door sits in. Para C13 states the link explicitly: the performance of some doorsets in Table C1 is tied to the minimum periods for elements of structure in Tables B1 and B2, and limitations on uninsulated glazing in fire doorsets are given in Table B3.
| Item | Position of door | Minimum integrity, European standard | Alternative, BS 476-22 |
|---|---|---|---|
| 1 | In a compartment wall separating buildings | Same as for the wall in which the door is fitted, but a minimum of 60 minutes | Same, minimum 60 minutes |
| 2(a) | In a compartment wall, if it separates a flat from a space in common use. This is the flat entrance door | E 30 Sa | FD 30 S |
| 2(b) | Enclosing a protected shaft forming a stairway wholly or partly above the adjoining ground, in a building used for flats, other residential, assembly and recreation, or office purposes | E 30 Sa | FD 30 S |
| 2(c) | Enclosing a protected shaft forming a stairway not described in 2(b) | Half the period of the wall it is fitted in, but 30 minutes minimum, with suffix Sa | Half, 30 minutes minimum, suffix S |
| 2(d) | Enclosing a protected shaft forming a lift or service shaft | Half the period of the wall it is fitted in, but 30 minutes minimum | Half, 30 minutes minimum |
| 2(e) | In a compartment wall, not described in 2(a) to 2(d) | Same as for the wall in which it is fitted, adding Sa only if the door is used for progressive horizontal evacuation under the guidance to requirement B1 | Same as the wall, adding S on the same condition |
| 3 | In a compartment floor | Same as for the floor in which it is fitted | Same as the floor |
| 4(a) | Forming part of the enclosures of a protected stairway, except as described in item 9 or 11(b) | E 30 Sa | FD 30 S |
| 4(b) | A lift shaft (para 3.99b) that does not form a protected shaft in 2(b), 2(c) or 2(d) | E 30 | FD 30 |
| 5(a) | Forming part of the enclosure of a protected lobby approach, or protected corridor, to a stairway | E 30 Sa | FD 30 S |
| 5(b) | Any other protected corridor | E 20 Sa | FD 20 S |
| 5(c) | A protected lobby approach to a lift shaft (paras 3.102 to 3.104) | E 30 Sa | FD 30 S |
| 6 | Giving access to an external escape route | E 30 | FD 30 |
| 7(a) | Sub-dividing corridors connecting alternative exits | E 20 Sa | FD 20 S |
| 7(b) | Sub-dividing dead-end portions of corridors from the remainder of the corridor | E 20 Sa | FD 20 S |
| 8 | Any door within a cavity barrier | E 30 | FD 30 |
| 9 | Any door forming part of the enclosure to a protected entrance hall or protected landing in a flat | E 20 | FD 20 |
| 10(a) | Any door forming part of the enclosure to a place of special fire hazard | E 30 | FD 30 |
| 10(b) | Any door forming part of the enclosure to ancillary accommodation in care homes (para 2.44, AD B Volume 2) | E 30 | FD 30 |
| 11(a) | In a dwellinghouse, between a dwellinghouse and a garage | E 30 Sa | FD 30 S |
| 11(b) | Forming part of the enclosures to a protected stairway in a single family dwellinghouse | E 20 | FD 20 |
| 11(c) | Within any fire resisting construction in a dwellinghouse not described elsewhere in Table C1 | E 20 | FD 20 |
Self-closers. Appendix C5: all fire doorsets, including to flat entrances and between a dwellinghouse and an integral garage, should be fitted with a self-closing device, except fire doorsets to cupboards, fire doorsets to service ducts normally locked shut, and fire doorsets within flats and dwellinghouses. So the garage door is expressly named as one that must self-close, while the doors on a protected stairway inside a single family dwellinghouse are not.
The Sa suffix. Table C1 note 2: unless pressurisation techniques complying with BS EN 12101-6 are used, these doors should either have a leakage rate not exceeding 3 m3/m/hour from head and jambs only when tested at 25 Pa under BS 476-31.1, or meet the additional Saclassification when tested to BS EN 1634-3. The suffix is not attached to every fire door: Table C1 leaves it off items 3, 4(b), 6, 8, 9, 10(a), 10(b), 11(b) and 11(c), and on item 2(e) it applies only where the door serves progressive horizontal evacuation.
FD 20 in practice. FD 20 doorsets are no longer manufactured or third-party certified, so an FD 30 door is normally fitted where Table C1 asks for E 20. Fitting the higher-rated door satisfies the requirement; it does not mean the requirement was 30 minutes.
Version note.The Table C1 above carries the banner “Effective until 29 September 2026”. The 2026 amendment, effective from 30 September 2026, adds the words “or an evacuation shaft” to items 2(b), 2(c), 4(a) and 5(a). None of the ratings in the table change.
Scotland, Wales and Northern Ireland
Approved Document B applies in England. Scotland uses the Building (Scotland) Regulations Technical Handbooks, Section 2 (Fire), which set out their own classifications and tables rather than Tables B1, B2 and C1. Wales has its own Approved Document B, which has diverged from the England version. Northern Ireland uses Technical Booklet E, which is broadly similar to Approved Document B but may sit on a different edition date. Check the document for the jurisdiction the building is in.
Related Calculators
The Part B Fire Calculator performs this same Table B2 lookup for a given purpose group, height and basement depth, and returns the out of scope result rather than a period where Table B2 reads “Not applicable”. Use the Fire Resistance Wall Calculator to specify wall constructions for a required rating, or the Fire Stopping Calculator for penetrations through compartmentation.
Figures on this page were read from the rendered pages of the Approved Document B Volume 1 PDF on gov.uk, 2019 edition incorporating the 2020, 2022 and 2025 amendments, collated with the 2026 and 2029 amendments. Table B2 carries the banner “Effective until 1 September 2029”; a 2029 amendment version of it is printed later in the same document. Approved Documents are updated periodically, so check the current edition on gov.uk before relying on any figure for a live project.
Next up: related pages
Frequently Asked Questions
Thirty minutes. Table B2 in Appendix B of Approved Document B gives rows 1(b) and 1(c) Dwellinghouse a period of 30 minutes in the "Up to 5" column, which is read on the height of the top floor above ground and not on the storey count. The notes to Table B2 add that for single storey buildings the periods under the heading "Up to 5" apply. Two qualifications sit on that cell. The dagger note reads: for compartment walls that separate buildings, the period is increased to a minimum of 60 minutes. And Table B1 item 3(b) treats the floor in the upper storey of a two storey dwellinghouse separately, at R 30 and EI 15 rather than REI 30, provided it is not over a garage or a basement.
For a dwellinghouse, Table B2 prints 60 minutes in the "Up to 11" and "Up to 18" columns, and both cells carry note 5: a minimum of 30 minutes in the case of three storey dwellinghouses, increased to 60 minutes minimum for compartment walls separating buildings. So a three storey house is not automatically a 60 minute building. For a block of flats, row 1(a) gives 60 minutes at "Up to 11" on both the sprinklered and the unsprinklered line, and 60 minutes at "Up to 18" on the sprinklered line only, because the unsprinklered line reads "Not permitted" above 11m and note 2 makes sprinklers mandatory there. Rows 2(a) residential institutional and 2(b) other residential are 60 minutes across both those bands, as is an unsprinklered office. An unsprinklered shop, assembly, industrial or storage building is already above 30 minutes at "Up to 5".
Approved Document B does not give one. Table B2 rows 1(b) and 1(c) print "Not applicable" in the "Up to 30" column, the "More than 30" column and the basement column for a lowest basement more than 10m deep. Note 4 says why, verbatim: "Very large (with a top storey more than 18m above ground level or with a 10m deep basement) or unusual dwellinghouses are outside the scope of the guidance provided with regard to dwellinghouses." There is no Approved Document period to quote for that building, so quoting 90 or 120 minutes for it would be inventing a figure the guidance declines to give. Design it with a fire engineer, normally to BS 9991, and agree the strategy with your building control body. A block of flats of the same height is a different purpose group, 1(a), and does have figures: 90 minutes up to 30m and 120 minutes above 30m, both on the sprinklered line.
Fire doorset provisions come from Table C1 in Appendix C, not from the period of the surrounding construction, so they are often a different number. A doorset forming part of the enclosures to a protected stairway in a single family dwellinghouse is E 20 (FD 20) under Table C1 item 11(b), and Appendix C5 exempts fire doorsets within flats and dwellinghouses from the self-closing requirement, so it needs no self-closer and Table C1 attaches no smoke suffix to it. A door in a compartment wall separating a flat from a space in common use, which is the flat entrance door, is E 30 Sa (FD 30 S) under item 2(a). The door between a dwellinghouse and a garage is E 30 Sa (FD 30 S) under item 11(a) and C5 names it expressly as one that must be self-closing. A protected corridor door is E 30 Sa (FD 30 S) only where the corridor is a lobby approach to a stairway (item 5(a)); any other protected corridor is E 20 Sa (FD 20 S) under item 5(b). FD 20 doorsets are no longer certified as products, so an FD 30 door is the practical way to satisfy an E 20 requirement.
No. Approved Document B applies in England only. Scotland follows the Building (Scotland) Regulations Technical Handbooks, Section 2 (Fire), which use their own classifications and tables. Wales has its own Approved Document B, which has diverged from the England version. Northern Ireland follows Technical Booklet E, which is broadly similar to Approved Document B but may sit on a different edition date. Check the document for the jurisdiction the building is in rather than assuming the England figures carry across.
Fire resistance is established by testing to BS EN 1363 and classified to BS EN 13501-2. Table B1 note 1 sets out what the letters mean: R is the resistance to fire in terms of loadbearing capacity, E is the resistance in terms of integrity, and I is the resistance in terms of insulation. An REI 60 element holds all three for 60 minutes. Table B1 also gives alternative minimum provisions tested to the relevant part of BS 476, and its note 1 warns that the national classifications do not automatically equate with the European ones, so a product cannot be assumed to hold a European class unless it has been tested to it.