Part G Hot Water Safety Standards

Hot water storage temperatures, TMV requirements, Legionella prevention, and unvented cylinder regulations, referencing Approved Document G: Sanitation, Hot Water Safety and Water Efficiency (2015 edition incorporating 2016 and 2024 amendments).

Hot Water Temperature Requirements (AD-G Section G3)

Hot Water Temperature Requirements (AD-G Section G3)
ParameterRequirementReason
Storage temperature≥ 60°CLegionella prevention
Distribution temperature≥ 55°C at return / furthest pointPrevent bacterial growth in pipework
Bath outlet (new dwellings)≤ 48°C (via TMV)Scald prevention
High-limit cut-out~90°C (non-self-resetting)Over-temperature safety
T&P relief valve90-95°C / 6-10 barPressure and temperature safety

Legionella Temperature Risk Zones

Legionella Temperature Risk Zones
Temperature RangeRisk LevelNotes
Below 20°CLow — bacteria dormantCold water should be kept below 20°C
20°C to 45°CHigh — rapid multiplicationDanger zone: avoid water sitting in this range
45°C to 50°CModerate — some bacteria surviveNot hot enough to reliably kill bacteria
50°C to 60°CLow — bacteria die slowlyTakes hours to kill; not sufficient for storage
Above 60°CVery low — bacteria killed quicklyStorage temperature target for safety

Unvented Cylinder Safety Devices (AD-G Diagram 1)

Unvented Cylinder Safety Devices (AD-G Diagram 1)
DeviceFunctionStandard
ThermostatControls operating temperature (60-65°C)Integral to cylinder
High-limit thermal cut-outShuts off heat at ~90°C, requires manual resetNon-self-resetting
Temperature & pressure relief valveOpens at 90-95°C or 6-10 barBS 6283-2
Expansion vessel / air gapAccommodates water expansion when heatedSized for cylinder volume
TundishVisible air break in T&P valve dischargeWithin 500 mm of valve
Discharge pipeSafely routes T&P discharge to safe pointMin. 1 pipe size larger than valve outlet

G3 Notification Requirements

G3 Notification Requirements
Work TypeNotifiable?Route
New unvented cylinder > 15 litresYesBuilding Control or competent person scheme
Replacement unvented cylinder (like-for-like)YesBuilding Control or competent person scheme
Vented cylinder installationNo (unless other notifiable work)N/A
Unvented cylinder ≤ 15 litresNoN/A (e.g. under-sink heaters)

Related Calculators

Use the Hot Water Cylinder Calculator for sizing, or the Pipe Sizing Calculator for distribution pipework. See also the Part G Water Calculator.

Always check the latest edition of Approved Documents on the Planning Portal (planningportal.co.uk) as regulations are updated periodically.